Product Features<br />

Energy Management System (EMS) Boiler Control (continued)<br />

Display Shows: Remote Sensor & Remote SP Mode<br />

Return<br />

Water<br />

Wired to Each<br />

TSBC <strong>Controller</strong><br />

EMS System Connections<br />

Lockout Indicator (LO)<br />

Soft Alarm (SO)<br />

Remote <strong>On</strong> / Off (Enable) (RO)<br />

Remote Setpoint (C+,C-)<br />

Outside Air<br />

Temperature<br />

( O + , O - )<br />

Boiler<br />

Circulator<br />

Remote System<br />

Temperature<br />

( R + , R - )<br />

Boiler Outlet<br />

Temperature<br />

( BO , BC )<br />

POWER<br />

ALARM<br />

Boiler<br />

Circulator<br />

Boiler Inlet<br />

Temperature<br />

(BI, BC)<br />

POWER<br />

ALARM<br />

Boiler<br />

Circulator<br />

POWER<br />

ALARM<br />

Remote System<br />

Temperature<br />

(R+,R-)<br />

Outside Air<br />

Temperature<br />

(O+, O-)<br />

Connects to<br />

Up to Eight<br />

Boilers<br />

System<br />

Circulator<br />

System<br />

Supply Water<br />

RJ 11 , RS 485<br />

Peer to Peer<br />

Network<br />

Remote Sensor & Remote SP Mode Application Diagram<br />

(Showing relevant connections for 3 boilers, typical for up to 8)<br />

Features<br />

Setpoints<br />

The setpoint is determined by the Remote Input (C+,C-)<br />

and operator sets the on and off points from the LCD<br />

display.<br />

Modulation Rate Control<br />

Boiler automatically modulates to maintain the Remote<br />

System Temperature (RST) at setpoint.<br />

Call for Heat<br />

The Call For Heat is determined by setpoint, on and off<br />

points and Remote System Temperature. If a Peer-To-<br />

Peer network is activated, a Call for Heat is also initiated<br />

when the Lead boiler modulation rate % is above an<br />

adjustable High Fire Rate Limit (Parameter 37) for too<br />

long a time.<br />

Options<br />

Warm Weather Shutdown (WWSD)<br />

If enabled, the WWSD will disable a boiler start when<br />

temperature is above a Warm Weather Shutdown<br />

(WWSD) setpoint.<br />

Outside Air Reset and Domestic Hot Water Priority input<br />

(DP) are ignored.<br />

Selecting This Control Mode<br />

To select Remote Sensor & Remote SP Mode set the<br />

following parameters:<br />

System Configuration Menu:<br />

Remote Control = “Remote SP”<br />

Remote System Temperature Sensor = Control<br />

Local / Remote Input (LR) = Closed (Jumper (LR) to (C) )<br />

Remote <strong>On</strong> / Off (Enable) Input (RO) = Closed (Jumper (LR)<br />

to (C) )<br />

When the Local / Remote Input (LR) is open, Remote Input<br />

(C+,C-) is ignored and Remote Sensor & Local SP Mode is<br />

active.<br />

If the Remote <strong>On</strong> / Off (Enable) (RO) input is opened, the<br />

Call For Heat Relay (CH) is de-energized.<br />

Peer-To-Peer Network<br />

To establish a Peer-To-Peer network follow the procedure<br />

provided on page 25.<br />

If the Peer-To-Peer network is activated the Lead boiler<br />

controls modulation rate and Call for Heat for all networked<br />

boilers. Up to 8 networked boilers are fired in “Unison” (all<br />

at the same modulation rate).<br />