Installation<br />

Communication (Continued)<br />

The TSBC communication selections are found on the Communication Menu. Press and hold the<br />

key to leave the Display Mode and access the Main Menu:<br />

MENU<br />

Use the keys scroll down to the Communication Menu and push the ENTER key:<br />

Communication Menu<br />

No. Range / Choices Parameter and Description<br />

90<br />

Peer to Peer<br />

Modbus<br />

91 1-247<br />

92<br />

93<br />

94<br />

95<br />

96<br />

9.6<br />

19.2<br />

38.4<br />

Odd<br />

Even<br />

None<br />

1-120<br />

Seconds<br />

97 1 to 8<br />

98 - - 6 - - - 321<br />

Protocol<br />

Selects between Peer-To-Peer (multiple boiler Lead/Lag control network) and<br />

a Modbus slave communication.<br />

Modbus Address<br />

Each boiler must be given a unique address. <strong>On</strong>ly visible when Protocol<br />

equals Modbus.<br />

Baud Rate<br />

Units are 1000 Bits Per Second (KBPS). <strong>On</strong>ly visible when Protocol equals<br />

Modbus.<br />

Parity<br />

<strong>On</strong>ly visible when Protocol equals Modbus.<br />

Timeout<br />

<strong>On</strong>ly visible when Protocol equals Modbus.<br />

Messages Rcvd<br />

Diagnostic tool used to confirm wiring and Modbus master configuration.<br />

<strong>On</strong>ly visible when Protocol equals Modbus.<br />

Messages Sent<br />

Diagnostic tool used to confirm wiring and Modbus master configuration.<br />

<strong>On</strong>ly visible when Protocol equals Modbus.<br />

Boiler Address<br />

Each boiler must be given a unique address. The boiler address assignment<br />

determines the boiler sequencing order. A value of 0 disables the network<br />

communications. <strong>On</strong>ly visible when Protocol equals Peer to Peer.<br />

<strong>On</strong>line Status<br />

Each space can be either the boiler address or a ‘ - ‘ depending on whether<br />

there is a boiler of that address on-line. <strong>On</strong>ly visible when Protocol equals<br />

Peer to Peer.<br />

Example: - - 6 - - - 321 indicates that boilers 6,3,2 and 1 are online<br />

TSBC Instruction Manual Page 24 of 48