Trouble Shooting<br />

Diagnostic Menu (Continued)<br />

System Menu<br />

Display<br />

Software Rev.<br />

S 3.24<br />

PCB Temperature<br />

70 F<br />

Clr BIT Hist<br />

No Action<br />

Clr Alarm Hist<br />

No Action<br />

Clr Run Time Cnt<br />

No Action<br />

Clr Cycle Cnt<br />

No Action<br />

Factory Defaults<br />

No Action<br />

Actual RST<br />

32 F<br />

Actual OAT<br />

-40 F<br />

Actual BOT<br />

32 F<br />

Actual BIT<br />

32 F<br />

Param Code<br />

Description<br />

Software Revision<br />

Displays current Software Revision.<br />

PCB Board Temperature<br />

The operating range for the control is 32 to 140 F.<br />

Clear Boiler Inlet Temperature (BIT) Memory<br />

No Action History remains unchanged.<br />

Yes<br />

Clears low BIT memory.<br />

Clear Alarm History Memory<br />

No Action History Remains unchanged.<br />

Yes<br />

Clears alarms memory.<br />

Clear Boiler Run Time Hour Accumulator Memory<br />

Boiler Run Time Hours are displayed in Display Mode as “Hours”.<br />

No Action Hours Remain unchanged.<br />

Yes<br />

Clears accumulated hours memory.<br />

Clear Boiler Start/Stop Cycle Accumulator Memory<br />

Boiler Start/Stop cycles are displayed in Display Mode as “Cycles”.<br />

No Action Hours Remain unchanged.<br />

Yes<br />

Clears accumulated cycles memory.<br />

Clear User Installed Parameter Memory<br />

No Action Currently set parameter values are unchanged.<br />

Set<br />

Sets all parameters back to their Factory Default values.<br />

Temperature Input Fine Calibration<br />

All inputs are factory calibrated. However, it may become necessary to field<br />

calibrate due to measuring errors resulting from long wire lengths or third party<br />

sensor use. This is a single point calibration tool. To gain the greatest<br />

benefit, it is recommended to calibrate as close as possible to the expected<br />

operating temperature and measure the temperature at the sensor location.<br />

Remote System Temperature (RST)<br />

Outside Air Temperature (OAT)<br />

Boiler Outlet Temperature (BOT)<br />

Boiler Inlet Temperature (BIT)<br />

Calibration Procedure:<br />

1. Select sensor that requires field calibration.<br />

2. Run boiler to rated condition.<br />

3. Enter the Actual RST, OAT, BOT and BIT.<br />

4. Display will flash back to the default (Note: Calibration number does<br />

not remain on screen).<br />

5. Calibration is complete. A one point calibration offset is calculated and<br />

applied.<br />

Parameter Code<br />

This number represents “Network Relevant” parameters. It can be used to<br />

ensure that these parameters are identical when establishing a Peer-To-Peer<br />

network.<br />

TSBC Instruction Manual Page 40 of 48