Trouble Shooting<br />
Diagnostic Menu (Continued)<br />
System Menu<br />
Display<br />
Software Rev.<br />
S 3.24<br />
PCB Temperature<br />
70 F<br />
Clr BIT Hist<br />
No Action<br />
Clr Alarm Hist<br />
No Action<br />
Clr Run Time Cnt<br />
No Action<br />
Clr Cycle Cnt<br />
No Action<br />
Factory Defaults<br />
No Action<br />
Actual RST<br />
32 F<br />
Actual OAT<br />
-40 F<br />
Actual BOT<br />
32 F<br />
Actual BIT<br />
32 F<br />
Param Code<br />
Description<br />
Software Revision<br />
Displays current Software Revision.<br />
PCB Board Temperature<br />
The operating range for the control is 32 to 140 F.<br />
Clear Boiler Inlet Temperature (BIT) Memory<br />
No Action History remains unchanged.<br />
Yes<br />
Clears low BIT memory.<br />
Clear Alarm History Memory<br />
No Action History Remains unchanged.<br />
Yes<br />
Clears alarms memory.<br />
Clear Boiler Run Time Hour Accumulator Memory<br />
Boiler Run Time Hours are displayed in Display Mode as “Hours”.<br />
No Action Hours Remain unchanged.<br />
Yes<br />
Clears accumulated hours memory.<br />
Clear Boiler Start/Stop Cycle Accumulator Memory<br />
Boiler Start/Stop cycles are displayed in Display Mode as “Cycles”.<br />
No Action Hours Remain unchanged.<br />
Yes<br />
Clears accumulated cycles memory.<br />
Clear User Installed Parameter Memory<br />
No Action Currently set parameter values are unchanged.<br />
Set<br />
Sets all parameters back to their Factory Default values.<br />
Temperature Input Fine Calibration<br />
All inputs are factory calibrated. However, it may become necessary to field<br />
calibrate due to measuring errors resulting from long wire lengths or third party<br />
sensor use. This is a single point calibration tool. To gain the greatest<br />
benefit, it is recommended to calibrate as close as possible to the expected<br />
operating temperature and measure the temperature at the sensor location.<br />
Remote System Temperature (RST)<br />
Outside Air Temperature (OAT)<br />
Boiler Outlet Temperature (BOT)<br />
Boiler Inlet Temperature (BIT)<br />
Calibration Procedure:<br />
1. Select sensor that requires field calibration.<br />
2. Run boiler to rated condition.<br />
3. Enter the Actual RST, OAT, BOT and BIT.<br />
4. Display will flash back to the default (Note: Calibration number does<br />
not remain on screen).<br />
5. Calibration is complete. A one point calibration offset is calculated and<br />
applied.<br />
Parameter Code<br />
This number represents “Network Relevant” parameters. It can be used to<br />
ensure that these parameters are identical when establishing a Peer-To-Peer<br />
network.<br />
TSBC Instruction Manual Page 40 of 48