Configuration & Tuning<br />
Setup Menu (Continued)<br />
230<br />
Max Setpoint<br />
230<br />
Boiler Design<br />
Boiler Set Up<br />
210<br />
190<br />
170<br />
150<br />
130<br />
110<br />
Hot Water Setpoint<br />
Design<br />
Temperature<br />
Set Up<br />
Temperature<br />
Min Setpoint<br />
210<br />
190<br />
170<br />
150<br />
130<br />
110<br />
Hot Water Setpoint<br />
Boiler<br />
Setpoint<br />
90<br />
90<br />
70<br />
Outdoor Air Temperature<br />
70<br />
Outdoor Air Temperature<br />
-20 0 20 40 60 80 100<br />
-20 0 20 40 60 80 100<br />
Outdoor Design<br />
Outdoor Set Up<br />
Outdoor Reset Graph<br />
Energy used by the hot water heating system can be greatly reduced by adjusting (resetting) the operating temperature<br />
setpoint as the outdoor temperature changes. Using this approach, the heat lost from the building is matched by the<br />
heat input to the building. The control utilizes a reset curve to set the relationship between outdoor temperature and<br />
boiler outlet temperature setpoint. The reset curve is determined from the “Set Up” and the “Design” conditions as<br />
shown in the above graph and described by parameters 45, 46, 47 and 48:<br />
No. Range / Choices Parameter and Description<br />
Outdoor Sensor<br />
Enables the Outside Air Temperature display and control logic:<br />
No<br />
Outside Air Input (O+O-) is ignored.<br />
No<br />
Display <strong>On</strong>ly Do Not Calculate setpoint based on outdoor<br />
44 Display <strong>On</strong>ly<br />
temperature; Display Outside Air Temperature.<br />
Outdoor Reset Outdoor Reset Calculate the temperature setpoint based on outdoor<br />
temperature using a reset curve defined by Outdoor<br />
Set Up, Boiler Set Up, Outdoor Design and Boiler<br />
Design parameters.<br />
Outdoor Set Up<br />
45 40 F to 100 F The Outdoor Set Up temperature is the outdoor temperature at which the<br />
Boiler Set Up temperature is supplied.<br />
46 140 F to 180 F<br />
Boiler Set Up<br />
The Boiler Set Up Temperature is the starting boiler water temperature of<br />
the reset ratio. If the building feels cool during mild outdoor conditions,<br />
the Boiler Set Up setting should be increased.<br />
47 -20 F to 50 F<br />
Outdoor Design<br />
The Outdoor Design Temperature is the outdoor temperature at which the<br />
Boiler Design temperature is supplied.<br />
48 150 F to 220 F<br />
Boiler Design<br />
The Boiler Design setting is the water temperature required to satisfy the<br />
building heat loss during the Outdoor Design temperature. If the building<br />
feels cool during cold outside conditions, the Boiler Design setting should<br />
be increased.<br />
TSBC Instruction Manual Page 32 of 48