Installation<br />
RS485 Modbus Network<br />
The TSBC includes a dependable Modbus communication network. This network allows boilers to be controlled and/or<br />
monitored by a remote system via a RS485 Modbus communication network. Each TSBC is a Modbus slave with the<br />
following available boiler information:<br />
Modbus Addresses<br />
Coil Address Description Read/Write coil = 0 coil = 1 Notes<br />
00001 Outdoor Air Reset Enable/Disable Disable Enable<br />
00002 Domestic Hot Water Priority (DHWP) Disable Enable<br />
00003 Local / Remote Local Remote<br />
00004 Remote <strong>On</strong> / Off Modbus Command Y Off <strong>On</strong> 1<br />
00005 Spare Input (Programmable) Off <strong>On</strong><br />
00006 Low Water Cutoff Switch Off <strong>On</strong> 2<br />
00007 Burner <strong>On</strong> / Off Switch Off <strong>On</strong> 2<br />
00008 Low Water Flow Off <strong>On</strong> 2<br />
00009 High and Low Gas Pressure Switches Off <strong>On</strong> 2<br />
00010 Operating or High Limit Off <strong>On</strong> 2<br />
00011 Low Combustion Air Flow Off <strong>On</strong> 2<br />
00012 Fuel Valve Energized Off <strong>On</strong><br />
00013 Flame Safeguard Alarm Off <strong>On</strong><br />
00014 Call For Heat (CFH) Off <strong>On</strong><br />
00015 General Alarm Off <strong>On</strong> 4<br />
00016 Vent Inducer Off <strong>On</strong><br />
00017 Boiler Pump Off <strong>On</strong><br />
00018 System Pump Off <strong>On</strong><br />
00019 Spare Output (Programmable) Off <strong>On</strong><br />
00020 State Boiler Disabled Off <strong>On</strong> 3<br />
00021 State Weather Shutdown Off <strong>On</strong> 3<br />
00022 State Lockout Off <strong>On</strong> 3<br />
00023 State Pump Purge Off <strong>On</strong> 3<br />
00024 State Limit Hold Off <strong>On</strong> 3<br />
00025 State Purge/Pilot Ign Off <strong>On</strong> 3<br />
00026 State Low Fire/Ignition Off <strong>On</strong> 3<br />
00027 State Main Ignition Off <strong>On</strong> 3<br />
00028 State Low Fire Hold Off <strong>On</strong> 3<br />
00029 State Boiler Running Off <strong>On</strong> 3<br />
00030 State Fan Post Purge Off <strong>On</strong> 3<br />
00031 State Pump Cool Down Off <strong>On</strong> 3<br />
00032 State Standby Off <strong>On</strong> 3<br />
00033 Annunciator Low Water Level Off <strong>On</strong> 4<br />
00034 Annunciator Off Switch Off <strong>On</strong> 4<br />
00035 Annunciator Low Water Flow Off <strong>On</strong> 4<br />
00036 Annunciator Fuel Limit Off <strong>On</strong> 4<br />
00037 Annunciator High Temp Limit Off <strong>On</strong> 4<br />
00038 Annunciator Low Air Flow Off <strong>On</strong> 4<br />
00039 Annunciator FSG Lockout Off <strong>On</strong> 4<br />
00040 Annunciator Outlet Temp Fail Off <strong>On</strong> 4<br />
00041 Annunciator Inlet Temp Fail Off <strong>On</strong> 4<br />
00042 Annunciator OA Temp Fail Off <strong>On</strong> 4<br />
TSBC Instruction Manual Page 26 of 48