Product Features<br />

Boiler Sequence (Continued)<br />

Multiple Boilers<br />

Setpoint<br />

SYSTEM<br />

TEMPERATURE<br />

185<br />

180<br />

175<br />

1<br />

2<br />

5<br />

High Fire Limit<br />

(Parameter 37)<br />

BOILER<br />

FIRING RATE<br />

100<br />

50<br />

2<br />

3<br />

4<br />

4 5<br />

0<br />

PLANT LOAD<br />

(# BOILERS REQURED)<br />

3<br />

2<br />

1<br />

0<br />

Start<br />

Lead Boiler<br />

Fast<br />

Load<br />

Change<br />

Start<br />

1 st Lag<br />

Slow<br />

Load<br />

Change<br />

Start<br />

2 nd Lag<br />

Stop<br />

2 nd Lag<br />

Stop<br />

1 st Lag<br />

Stop<br />

Lead Boiler<br />

1<br />

2<br />

3<br />

4<br />

Boiler Start and Stop Peer-To-Peer Network Sequence Diagram<br />

(3 boiler system shown, typical for up to 8 boilers)<br />

- Lead Boiler Start<br />

Water temperature is below the setpoint by more than the “<strong>On</strong> Point” differential.<br />

- Temperature Based Lag Boiler Start<br />

Water temperature is below the setpoint by more than the “<strong>On</strong> Point” differential for longer than the adjustable<br />

time delay (“Boiler <strong>On</strong> Delay” parameter).<br />

- Modulation % Based Lag Boiler Start<br />

The boiler modulation rate has been above the adjustable limit (“LL Start Trigger” parameter) for longer than the<br />

time delay.<br />

- Lag Boiler Stop<br />

The boiler modulation rate has been below the adjustable limit (“LL Stop Trigger” parameter) for longer than the<br />

time delay. Additionally, lag boilers are stopped when water temperature is above the setpoint by more than the<br />

“Off Point” differential for longer than the “Boiler Off Delay” parameter).<br />

5<br />

- Lead Boiler Stop<br />

The last boiler remains on line until the water temperature is above the “Off Point” setpoint for longer than the<br />

time delay.<br />

Notes<br />

- The “Boiler Address” parameter assignment determines the boiler sequencing order.<br />

- The Lead Boiler automatically rotates (when “Rotate” parameter is enabled) based on field adjusted time<br />

(“Rotate After” parameter, default is 168 hours). When rotating, the lead boiler will move to the end of the lag<br />

order and the 1 st lag boiler will become the lead. The rest of the boilers will then move up in the lag order<br />

accordingly.<br />

- Lead Boiler is the first boiler to turn on and the last boiler to turn off, (First <strong>On</strong>, Last Off, FOLO).<br />

- Lag Boilers are turned on in order and turned off in reverse order, (First <strong>On</strong>, Last Off, FOLO).<br />

- Tripped boilers are replaced without waiting for the Boiler <strong>On</strong> Delay timer. If a tripped boiler becomes available it<br />

is returned to service.<br />

TSBC Instruction Manual Page 8 of 48