Trouble Shooting<br />

Diagnostic Menu<br />

All values shown in Diagnostic Menu are for display only and cannot be adjusted by the operator. Press and hold the<br />

key to leave the Display Mode and access the Main Menu.<br />

MENU<br />

Use the keys scroll down to the Diagnostic Menu and push the ENTER key.<br />

Boiler Inlet Temperature History<br />

Display<br />

13:31 09/10/06<br />

BOT Sensor Fail<br />

8:45 09/10/06<br />

Low Temp: 130F<br />

8:45 09/10/06<br />

Low for 1:00:02<br />

Description<br />

FAULT HISTORY<br />

The last 10 alarms are stored in memory. Use the arrow keys to scroll through<br />

the alarms. Each alarm is displayed with the time and date it occurred.<br />

BIT HISTORY<br />

The last 10 Low Inlet Temperature Events are stored in memory. Each time<br />

the boiler inlet temperature is less than the “Min In H2O Temp.” parameter, a<br />

low temperature event is recorded. The BIT History screen automatically<br />

toggles between the “lowest temperature for the event” and “Duration Below<br />

Setpoint” displays and provides time and date of each event.<br />

SYSTEM<br />

Items provided by this menu are shown on page 40.<br />

DHW Priority<br />

Off<br />

Local/Remote<br />

Off<br />

Remote <strong>On</strong>/Off<br />

Off<br />

DISCRETE INPUTS<br />

These screens provide a convenient way to trouble shoot wiring during the<br />

installation phase. Each screen provides the status of a controller input.<br />

These displays show the status of the corresponding Discrete Input.<br />

Spare Input<br />

Off<br />

Low Water Cutoff<br />

Off<br />

Burner <strong>On</strong> / Off<br />

Off<br />

Low Water Flow<br />

Off<br />

Fuel Limit<br />

Off<br />

PLEASE NOTE<br />

These displays provide limit string monitoring status. These inputs are only<br />

monitored when there is a Call For Heat. Additionally, if one of these items is<br />

‘open’, items down stream are not monitored.<br />

Oper./High Limit<br />

Off<br />

Low Air Flow<br />

Off<br />

Fuel Energized<br />

Off<br />

FSG Alarm<br />

Off<br />

These displays show the status of the corresponding Discrete Input.<br />

TSBC Instruction Manual Page 38 of 48