Application Note<br />
04-0629-2<br />
Product: S4<br />
Subject: Programming the S4 for Utilinet Radio Operation<br />
Date: 8/27/2004<br />
Description:<br />
The Utilinet module relies on certain inputs from relay 4 for its operation. As a result there are a few<br />
minimum programming requirements for the S4 (using 1132Prog).<br />
Relays:<br />
Set Relay 4 to Load Control (“LC”), “Used” in Normal Mode and Normal Off State to “Closed”.<br />
<strong>Landis+Gyr</strong> Inc.<br />
2800 Duncan Rd. Tel: (800) 777-2774<br />
Lafayette, IN 47904-5012 Fax: (765) 742-0936
<strong>Landis+Gyr</strong><br />
Application Note<br />
04-0629-2<br />
TOU Rates Schedule:<br />
Set AX/RX Only? to “Yes”, and Schedule Relay? to “Yes”<br />
<strong>Landis+Gyr</strong> Inc.<br />
2800 Duncan Rd. Tel: (800) 777-2774<br />
Lafayette, IN 47904-5012 Fax: (765) 742-0936
<strong>Landis+Gyr</strong><br />
Application Note<br />
04-0629-2<br />
Also, Set all Switchpoints to “OFF” in the Rates Schedule<br />
<strong>Landis+Gyr</strong> Inc.<br />
2800 Duncan Rd. Tel: (800) 777-2774<br />
Lafayette, IN 47904-5012 Fax: (765) 742-0936
<strong>Landis+Gyr</strong><br />
Application Note<br />
04-0629-2<br />
Modem Disable:<br />
The modem functionality also needs to be disabled. If modem features are not disabled then the<br />
communication port in the meter will try to use modem commands which could possibly confuse the Utilinet<br />
module. To disable the modem go to Program Values on the third tab select ‘None’ in the Modem Data field.<br />