FREESTANDING DHW CYLINDERS<br />

Model Freestanding DHW cylinder Inst. water heating cylinder Inst. water heating cylinder<br />

– Type HSTP 200 HSTP 300 HSTP 400 SBS 800 W SBS 1000 W SBS 1500 W SBS 800 W SOL SBS 1000 W SOL SBS 1500 W SOL<br />

– Part no. 071264 071267 071270 227568 227569 227570 227571 227572 227573<br />

Application<br />

– Nominal capacity l 200 300 400 800 1,000 1,500 800 1,000 1,500<br />

Connection details<br />

– Mode of operation<br />

– Dual/single circuit cylinder 1) • • •<br />

Key<br />

• Available, or yes.<br />

1) Dual-circuit system for reheating during the day, subject to demand.<br />

2) Permissible heating side 0.3/3 MPa/bar.<br />

3) The mixed water volume has a service temperature of 40 °C which is<br />

based on a cold water temperature of 15 °C and a cylinder water<br />

temperature of 65 °C (with respect to the operational state).<br />

Combined DHW and<br />

heating water buffer cylinder<br />

Combined DHW and<br />

heating water buffer cylinder<br />

– Water connection<br />

(external thread) below/above G1" / G1" G1 ¼" G1 ¼"<br />

– DHW circulation connection G ½" – – – – – –<br />

– Heat pump connection – G1 ½" G1 ½" G2" G1 ½" G1 ½" G2"<br />

– Heating circuit connection – G1 ½" G1 ½"<br />

– Connection for opt. heat source – G1 ½" G1 ½"<br />

– Permiss. op. pressure MPa/bar 0.6 / 6 0.6 / 6 2) 0.6 / 6 2)<br />

– Mixed water volume of 40 °C 3) l 397 590 792 – – – – – –<br />

– Stand-by power consumption<br />

at 65 °C / 24 h kWh 1.9 2.2 2.7 – – – – – –<br />

– Connected load and<br />

voltage 4)<br />

Dual-circuit operation: 2/4 kW, 4/4 kW<br />

1/N/PE ~ 230 V; 2/6 kW, 3/6 kW, 4/6 kW,<br />

6/6 kW | 3/N/PE ~ 400 V<br />

Single circuit operation: 2 kW, 4 kW<br />

1/N/PE ~ 230 V; 2 kW, 3 kW, 4 kW, 6 kW<br />

3/N/PE ~ 400 V<br />

– –<br />

– Protection level IP 24 (splash-proof) – –<br />

– Test symbols VDE / GS – –<br />

Equipment level<br />

– Thermal insulation<br />

Permanently fixed/removable5) – Steel inner cylinder, enamel-<br />

•/– •/– •/– –/• –/• –/• –/• –/• –/•<br />

coated, with prot. anode • • • – – – – – –<br />

– Temperature range<br />

– Temperature limit<br />

°C 35 to 82 – – – – – –<br />

can be adjusted to °C 45 to 60 – – – – – –<br />

– Contents HE DHW l – – – 41 53 65 41 53 65<br />

– Area Solar internal indirect coil m2 – – – – – – 2.4 3.0 3.6<br />

– Colour Pearl white Thermal insulation white Thermal insulation white<br />

Weight and dimensions<br />

– Height6) mm 1,570 1,585 1,755 1,840 2,250 2,190 1,840 2,250 2,190<br />

– Height when tilted mm – – – 1,880 2,285 2,225 1,880 2,285 2,225<br />

– Width mm ø 550 ø 650 ø 700 ø 790 ø 790 ø 1,000 ø 790 ø 790 ø 1,000<br />

– Depth mm 690 790 840 910 910 1120 910 910 1,120<br />

– Wet weight7) kg 255 368 485 950 1,175 1,736 995 1,220 1,791<br />

4) Regulations vary according to local power supply company; to be connected only<br />

by a qualified electrician.<br />

5) Thermal insulation WD SBS as accessory, thickness 110 mm.<br />

6) With water connector.<br />

7) Before installing ensure the floor has sufficient load-bearing capacity.<br />

58 | 59