Alarm Worksheet<br />

Advanced Settings Dialog Box<br />

The Activation field, which contains either a value or an WS tag, specifies, in seconds, the amount of time<br />

each alarm in the Alarm Group must remain continuously in its alarm condition before becoming active. This<br />

option is useful to avoid generating alarms on intermittent conditions (e.g.: noise). If this field is left in blank, the<br />

alarm becomes active as soon as its condition is true.<br />

The Normalization field, which contains either a value or an WS tag, specifies, in seconds, the amount of time<br />

each alarm in the Alarm Group must remain continuously out from its alarm condition before becoming<br />

normalized. This option is useful to avoid normalizing alarms on intermittent conditions (e.g.: noise). If this field<br />

is left in blank, the alarm becomes normalized as soon as its condition is no longer true.<br />

The Time Stamp/Value field is a combo-box that lets you select the type of time stamp to be maintained by the<br />

Tag for the last significant Alarm activity, along with the value of the Tag at that time. You can select the type of<br />

activity that updates the time stamp:<br />

• Activation/Norm (default): The time when the dead band ended — that is, when the alarm becomes<br />

activated or normalized.<br />

• Last Tag Change: The time when the value of the tag last changed during the dead band.<br />

• Start Condition: The time when the dead band started.<br />

The Email Settings button opens a dialog<br />

box that allows you to specify settings for<br />

email messages that can be sent when<br />

Alarms occur. Email (SMTP) setting must<br />

be configured prior to use of the Alarm<br />

Emails. Attachments are not allowed in this<br />

dialog, but attachments can be emailed<br />

using WS built-in functions.<br />

21–4 InduSoft Web Studio