Contents<br />

<strong>IWS</strong> <strong>Training</strong> <strong>Guide</strong><br />

<strong>IWS</strong> Proprietary File and Database Format for Alarm History<br />

When you enable the alarm history file for a group, <strong>IWS</strong> saves the alarm events to a history database,<br />

according to the File Format configured for the Alarm History. Each Alarm Event is saved on a new line in the<br />

Alarm History file, separated by the vertical bar (pipe) character. The format of the Alarm History data saved in<br />

the history file or to a SQL relational database is described in the following table.<br />

P1 | P2 | P3 | P4 | P5 | P6 | P7 | P8 | P9 | P10 | P11 | P12 | P13 | P14 | P15 | P16 | P17 | P18 | P19 | P20 | P21 | P22 | P23 | P24 | P25 | P26<br />

P1 | P2 | P3 | P4 | P5 | P6 | P7 | P8 | P9 | P10 | P11 | P12 | P13 | P14 | P15 | P16 | P17 | P18 | P19 | P20 | P21 | P22 | P23 | P24 | P25 | P26<br />

..<br />

P1 | P2 | P3 | P4 | P5 | P6 | P7 | P8 | P9 | P10 | P11 | P12 | P13 | P14 | P15 | P16 | P17 | P18 | P19 | P20 | P21 | P22 | P23 | P24 | P25 | P26<br />

Field<br />

Number<br />

Field Name Data Type Remarks<br />

P1 Version Number<br />

P2<br />

P3<br />

Al_Start_Time<br />

DateTime<br />

This field is created only when the File Format is<br />

Proprietary. Current version: 003<br />

Timestamp indicating when the alarm started.<br />

When the File Format is Proprietary, <strong>IWS</strong> saves the<br />

Date (MM/DD/YYYY) in one field and the Time<br />

(HH:MM:SS.MSS) in the next field.<br />

P4 Al_Tag String Tag Name that caused the Alarm<br />

P5 Al_Message String Alarm message<br />

P6 Al_Ack Number<br />

P7 Al_Active Number<br />

0: Indicates the alarm was acknowledged or does not<br />

require acknowledgment<br />

1: Indicates the alarm was not acknowledged<br />

0: Indicates the alarm is not active<br />

1: Indicates the alarm is active<br />

P8 Al_Tag_Value Number Tag value when the alarm event occurred<br />

P9 Al_Prev_Tag_Value Number<br />

P10 Al_Group Number Alarm Group Number<br />

P11 Al_Priority Number Alarm Priority Number<br />

P12 Al_Selection String Alarm Selection value<br />

P13 Al_Type Number<br />

P14 Al_Ack_Req Number<br />

P15<br />

P16<br />

Al_Norm_Time<br />

DateTime<br />

Tag value that occurred before the alarm event. This<br />

field only exists for Version >=3<br />

1: HiHi<br />

2: Hi(On)<br />

4: Lo(Off)<br />

8: LoLo<br />

16: Rate(Change)<br />

32: Deviation+<br />

64: Deviation-<br />

0: Requires acknowledgement (Ack)<br />

1: Does not require acknowledgement<br />

Timestamp indicating when the alarm was normalized.<br />

When the File Format is Proprietary, <strong>IWS</strong> saves the<br />

Date (MM/DD/YYYY) in one field and the Time<br />

(HH:MM:SS.MSS) in the next field.<br />

InduSoft Web Studio 19–3