Chapter 19. <strong>IWS</strong> File/Database Configuration<br />

In this Chapter, we will look at how to configure database connections for Trends, Alarms, Events and the Grid<br />

Object. In subsequent chapters, we will cover the Trending, Alarm, Event and Grid Objects and Worksheets in<br />

further detail.<br />

<strong>IWS</strong> provides automatic database storage and retrieval for Trend data, Alarms, Events, and the Grid Object.<br />

This data can be stored in either the <strong>IWS</strong> proprietary database format (to local files), or to a relational<br />

database (local or remotely located) using the built-in ADO.NET interface. The Grid Object can only be used<br />

with the built-in ADO.NET interface (or with Class Objects or Text files).<br />

Using the <strong>IWS</strong> Proprietary File Format<br />

Trend Data, Alarm Data and Event Data can all be stored (and retrieved) in files on the local computer using the<br />

built-in <strong>IWS</strong> proprietary format. The advantage of the <strong>IWS</strong> proprietary database format is that the data is very<br />

compact and a 3 rd party database is not required.<br />

The following chart explains where the database configuration for each Task is located:<br />

Task<br />

Alarms<br />

Events<br />

Trend<br />

Interface<br />

• From the Main Menu Bar, select Project Settings, and then select the Options<br />

Tab. In the Alarm History and Events section, select the Proprietary option in the<br />

History Format combo box.<br />

• From the Main Menu Bar, select Project Settings, and then select the Options<br />

Tab. In the Alarm History and Events section, select the Proprietary option in the<br />

History Format combo box.<br />

• In a Trend Worksheet, select the Proprietary option in the History Format combo<br />

box.<br />

Notes:<br />

• Both the Alarms and Events must be saved in the same format (i.e. <strong>IWS</strong> Proprietary or to a Relational<br />

Database). If stored to a Relational Database, the Relational Databases can be different<br />

• Each Trend Worksheet can be individually configured to store data in the <strong>IWS</strong> Proprietary format or to<br />

a Relational Database.<br />

InduSoft Web Studio 19–1