INSTALLATION AND OPERATION MANUAL - Wood Pellet Stoves
INSTALLATION AND OPERATION MANUAL - Wood Pellet Stoves
INSTALLATION AND OPERATION MANUAL - Wood Pellet Stoves
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
PLANNING YOUR <strong>INSTALLATION</strong><br />
MANUFACTURED (MOBILE) HOME INSTAL-<br />
LATION<br />
Freestanding Model – Advantage II-T C FS<br />
In addition to the standard installation instructions,<br />
the following instructions may be required by local,<br />
state or federal building codes:<br />
• Stove must be permanently bolted to the floor.<br />
• An outside air inlet must be provided for combustion<br />
and be unrestricted while unit is in use.<br />
Use a galvanized or stainless steel pipe for the<br />
duct (the outside air inlet on the stove is 1 5/8"<br />
diameter).<br />
• Stove must be permanently electrically<br />
grounded to the steel chassis of the home. The<br />
location selected for ground attachment to the<br />
stove must be dedicated for this purpose.<br />
• See pages 13 through 18 for additional information<br />
on venting requirements.<br />
• Do not install appliance in a sleeping room.<br />
• The structural integrity of the manufactured<br />
home floor, walls, ceiling and roof must be<br />
maintained.<br />
NOTE: The grounding of this product, at installation,<br />
must comply with NFPA-70 standards,<br />
CSA C22.1 in Canada, as well as<br />
any local codes.<br />
24 ¾”<br />
Model – Advantage II-T C FS<br />
Pedestal Air Inlet<br />
25”<br />
12 ½”<br />
Outside Air Inlet<br />
1 5/8" diameter<br />
6 7/8”<br />
MANUFACTURED (MOBILE) HOME EXHAUST VENT PIPE<br />
<strong>INSTALLATION</strong> GUIDELINES<br />
Use only “PL” pellet vent pipe listed to UL 641 and ULC<br />
S609. The pipe should extend at least 3 feet above the part<br />
of the roof through which it passes. The top of the pipe<br />
should be at least 2 feet above the highest required elevation<br />
of any part of the manufactured (mobile) home within 10 feet<br />
of the pipe (see page 14, Manufactured [Mobile] Home<br />
Chimney Height Requirements).<br />
If the exhaust vent exits the manufactured (mobile) home at a<br />
location other than the roof, and exits at a point 7 feet or less<br />
above the ground level on which the manufactured (mobile)<br />
home is position a guard or method of enclosing the pipe<br />
shall be provided at the point of exit for a height of up to 7<br />
feet. The openings, if any, in this guard shall not allow a 3/4”<br />
rod to pass through. A 1/2” rod could pass through but should<br />
not be able to touch the pipe when inserted through the opening<br />
a distance of 4 inches.<br />
Bolt<br />
PAGE 8<br />
www.<strong>Pellet</strong>King.com<br />
Bolt<br />
Floor Protector<br />
Floor<br />
Steel Chassis<br />
Ground<br />
To Chassis