<strong>CPG</strong>(090/102/120/150)2104B*/7B* THREE PHASE 460-575/60 HZ BELT DRIVE WIRING DIAGRAM<br />

HIGH VOLTAGE!<br />

DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS<br />

UNIT. MULTIPLE POWER SOURCES MAY BE PRESENT. FAILURE TO<br />

DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY OR DEATH.<br />

L1<br />

NOTE 3<br />

L1<br />

4<br />

5<br />

9<br />

R<br />

F<br />

2<br />

1<br />

IIC<br />

TB1<br />

8<br />

ECON<br />

7 10<br />

G<br />

TO THERMOSTAT<br />

W2<br />

NOTE 5<br />

INSTALLER/SERVICEMAN<br />

THE STATUS LIGHT ON THE FURNACE CONTROL MAY BE USED AS A GUIDE TO<br />

TROUBLESHOOTING THIS APPLIANCE. STATUS LIGHT CODES ARE AS FOLLOWS:<br />

STATUS LIGHT<br />

ON<br />

OFF<br />

CC1<br />

1 BLINK<br />

CC2<br />

2 BLINKS<br />

3 BLINKS<br />

4 BLINKS<br />

5 BLINKS<br />

6 BLINKS<br />

BC<br />

H C<br />

T1<br />

3<br />

6<br />

W1<br />

T1<br />

FS<br />

D1<br />

COMP1<br />

RCCF2<br />

T1<br />

EM<br />

12<br />

11<br />

SUPPLY VOLTAGE<br />

460-575/3/60<br />

T2<br />

T3<br />

RCCF1<br />

T2<br />

T3<br />

C<br />

F<br />

2 4 WH<br />

R<br />

460V OR APPROPRIATE INPUT VOLTAGE<br />

1 3<br />

TR<br />

460V OR APPROPRIATE INPUT VOLTAGE<br />

1<br />

3<br />

PS<br />

LS<br />

HPS1<br />

T2<br />

24V<br />

ALS<br />

LPS1<br />

EQUIPMENT STATUS<br />

NORMAL OPERATION<br />

NO POWER OR<br />

INTERNAL CONTROL<br />

IGNITION FAILURE<br />

OPEN ROLLOUT<br />

SWITCH<br />

OPEN AUX. LIMIT<br />

SWITCH<br />

PRESSURE SWITCH<br />

OPEN<br />

PRESSURE SWITCH CLOSED<br />

WITHOUT INDUCER ON<br />

C<br />

OPEN LIMIT SWITCH<br />

TR<br />

RS<br />

FALSE FLAME SENSED<br />

COMPRESSOR<br />

OUTPUT DELAY<br />

F<br />

COMP2 T2<br />

BC<br />

BC<br />

CC1<br />

CM2<br />

CC2<br />

Y1 Y<br />

Y2<br />

CM1<br />

CC1<br />

T3 CC2<br />

IGN<br />

FS<br />

VMR<br />

LPS2<br />

C<br />

TB1<br />

GV<br />

HPS2<br />

C1<br />

PLF<br />

NOTE<br />

2<br />

VM<br />

NOTE 3<br />

L2<br />

IIC<br />

BC<br />

9<br />

8<br />

7<br />

CHECK<br />

C2<br />

------<br />

CHECK INPUT POWER<br />

CHECK FUSE ON CONTROL<br />

REPLACE CONTROL<br />

<strong>GAS</strong> FLOW<br />

<strong>GAS</strong> PRESSURE<br />

<strong>GAS</strong> VALVE<br />

FLAME SENSOR<br />

FLAME ROLLOUT<br />

BAD SWITCH<br />

AUX. LIMIT OPEN<br />

CHECK<br />

PRESSURE SWITCH<br />

CHECK<br />

PRESSURE SWITCH<br />

MAIN LIMIT OPEN<br />

BAD SWITCH<br />

STICKING <strong>GAS</strong> VALVE<br />

3 MIN. COMP.<br />

ANTI-CYCLE TIMER<br />

6<br />

5<br />

4<br />

3<br />

2<br />

1<br />

L2 L3<br />

COMPONENT LEGEND<br />

ALS<br />

BC<br />

COMP<br />

CM<br />

CC<br />

EM<br />

F<br />

FC<br />

FS<br />

GND<br />

GV<br />

HPS<br />

IBR<br />

IIC<br />

IGN<br />

LPS<br />

LS<br />

PLF<br />

PS<br />

RS<br />

TB1<br />

TR<br />

VM<br />

VMR<br />

NOTES<br />

AUXILIARY LIMIT SWITCH<br />

BLOWER CONTACTOR<br />

COMPRESSOR<br />

CONDENSER MOTOR<br />

COMPRESSOR CONTACTOR<br />

EVAPORATOR MOTOR<br />

FUSE<br />

FAN CAPACITOR<br />

FLAME SENSOR<br />

EQUIPMENT GROUND<br />

<strong>GAS</strong> VALVE<br />

HIGH PRESSURE SWITCH<br />

INDOOR BLOWER RELAY<br />

INTEGRATED IGNITION CONTROL<br />

IGNITOR<br />

LOW PRESSURE SWITCH<br />

LIMIT SWITCH<br />

FEMALE PLUG/CONNECTOR<br />

PRESSURE SWITCH<br />

ROLLOUT SWITCH<br />

TERMINAL BLOCK (24V SIGNAL)<br />

TRANSFORMER<br />

VENT MOTOR<br />

VENT MOTOR RELAY<br />

1. REPLACEMENT WIRE MUST BE THE SAME<br />

SIZE AND TYPE OF INSULATION AS ORIGINAL.<br />

(USE COPPER CONDUCTOR ONLY).<br />

2. ACCESSORY ECONOMIZER PLUG ADJACENT<br />

TO BLOWER HOUSING IN RETURN AIR<br />

COMPARTMENT. REMOVE MALE PLUG AND<br />

ATTACH FEMALE PLUG TO THE ECONOMIZER<br />

ACCESSORY.<br />

3. L1 AND L2 ON IIC CONTROL IS 24V INPUT.<br />

4. USE COPPER CONDUCTORS ONLY.<br />

USE NEC CLASS 2 WIRE.<br />

5. FOR TWO STAGE OPERATION REMOVE<br />

W1 TO W2 WIRE JUMPER.<br />

WIRE CODE<br />

BK BLACK<br />

BL BLUE<br />

BR BROWN<br />

GR GREEN<br />

OR ORANGE<br />

PK PINK<br />

PU PURPLE<br />

RD RED<br />

WH WHITE<br />

YL YELLOW<br />

YL/PK YELLOW WITH<br />

PINK STRIP<br />

BL/PK BLUE WITH<br />

PINK STRIP<br />

THERMOSTAT<br />

FIELD WIRING<br />

2 STAGE COOLING<br />

W WH W<br />

G GR G<br />

R RD R<br />

Y1 YL Y1<br />

Y/Y2 PK Y2<br />

C BL C<br />

O OR O<br />

STAT<br />

TB1<br />

NO ECONOMIZER<br />

W WH W<br />

G GR G<br />

R RD R<br />

Y1<br />

Y/Y2 YL Y2<br />

C BL C<br />

O OR O<br />

TB1<br />

WITH ECONOMIZER OPTION<br />

W<br />

G<br />

R<br />

Y1<br />

Y/Y2<br />

C<br />

O<br />

TB1<br />

FACTORY WIRING<br />

LINE VOLTAGE<br />

LOW VOLTAGE<br />

OPTIONAL<br />

HIGH VOLTAGE<br />

FIELD WIRING<br />

HIGH VOLTAGE<br />

LOW VOLTAGE<br />

WH<br />

GR<br />

RD<br />

YL<br />

BL<br />

OR<br />

STAT<br />

W<br />

G<br />

R<br />

Y<br />

C<br />

O<br />

STAT<br />

460-575/3/60 0140L00551 REV B<br />

Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring.<br />