CSX-K SERIES<br />
(Enclosure Manufacturer: Hubbell-Killark)<br />
Explosion Proof FVNR Combination Motor Starters – NEMA 7/9, 1/4 HP – 500 HP<br />
IEC Contactor with adjustable thermal Overload (Class 10). Oversized Control Power Transformer<br />
(<strong>opt</strong>ional). External Machined Flange Joint Design. Units are assembled, pre-wired and ready to go.<br />
Integral Cast Mounting Feet. Units come <strong>standard</strong> with Hinged Covers. S.S. (316) Captive Quick<br />
Thread Cover Bolts (<strong>opt</strong>ional). Ground Lug Package. Steel Mounting Pan. Enclosures Cast From<br />
Copper – Free Aluminum – Max 0.25% Copper Content. Aluminum, Stainless Steel Shot or Sandblasted<br />
Natural Finish. Enclosures Suitable for NEMA 4X. Cast Aluminum and Stainless Steel Hinge. <strong>Inc</strong>ludes<br />
a Molded Case Circuit Breaker with through-the-door handle.<br />
Technical Data and Specifications<br />
ENCLOSURE<br />
Applications<br />
• Designed to enclose electrical and/or electronic equipment and<br />
protect against harsh, industrial environments.<br />
Standards<br />
• UL 508 Type 3R, 4, 12 and 13<br />
• CSA Type 3R, 4, 12 and 13<br />
Complies with:<br />
• NEMA Type 3R, 4, 12 and 13<br />
• IEC 529, IP66<br />
Construction<br />
• Body and cover are formed from 16 gauge steel.<br />
• Smooth, continuously welded sea<strong>ms</strong> without knockouts, cutouts,<br />
or holes.<br />
• Formed lip on enclosure to exclude flowing liquids and<br />
contaminants.<br />
• 14 gauge welded brackets provide for enclosure mounting.<br />
• Continuously hinged cover has 304 stainless steel hinges and<br />
provides 180º opening.<br />
• Door latches feature the added safety of quarter turn slot requiring<br />
use of tool for opening.<br />
• Quarter turn latches formed from black zinc diecast.<br />
• Oil resistant gaskets are permanently secured.<br />
• Models larger than 4”x4” include a removable 14 gauge<br />
galvanized inner panel.<br />
Finish<br />
• Cover and enclosure are finished in recoatable smooth ANSI/ASA<br />
61 gray powder coating.<br />
• Inner panels are unpainted galvanized steel, (50-200HP) and<br />
above are painted white.<br />
CONTACTOR<br />
Standards<br />
• Compact frame sizes from 7A to 250A<br />
• Common accessories for all contactor sizes<br />
• Panel or 35mm DIN rail mountable<br />
• Simple to exchange coils<br />
• Finger-touch protection<br />
• Front and side mountable auxiliary contact blocks<br />
• Replaceable main contacts for entire line<br />
• Positively driven contacts and operations<br />
• Front and side mounted auxiliary contacts<br />
• Wide coil voltage selection<br />
• Designed to perform over 1 million electrical and 10 million<br />
mechanical operations<br />
Certifications:<br />
• cULus<br />
• IEC 60947<br />
• CE<br />
OVERLOAD<br />
Standards<br />
• Phase failure/unbalance sensitivity<br />
• Ambient temperature compensation<br />
• Isolated N.C. “Trip” and N.O. “Alarm” auxiliary contacts<br />
• Class 10 tripping characteristics<br />
• “Trip Free” design<br />
• Field adjustable trip current setting<br />
• Test/Reset button<br />
• Selectable Manual or Automatic Reset<br />
• Separate mounting capability via screws or DIN rail<br />
CONTROL POWER TRANSFORMER<br />
Standards<br />
• Control Power Transformers meet or exceeds the<br />
<strong>standard</strong>s established by UL, CSA, IRC, ANSI, NEMA.<br />
Standard File No. VA Size<br />
UL (ANSI/UL 506) E50394<br />
All Units<br />
CSA (C22-2 No. 66) LR3902<br />
All Units<br />
IEC 989<br />
All Molded Units<br />
NEMA (ST-1)<br />
All Units<br />
Core & Coils<br />
• High quality, high permeability silicon steel laminations.<br />
• All-welded construction.<br />
• Computer designed copper wound coils with <strong>opt</strong>imum turns ratio.<br />
Finger Safe Terminal Covers<br />
• Finger safe terminal covers for both fused and un-fused terminals, in<br />
a clear, see through finish, are available for all molded transformer<br />
series units.<br />
Standard Secondary Fuse Clips<br />
• Each transformer has a single secondary and comes with a factory<br />
installed secondary fuse kit. (fuses are not included.)<br />
• Accommodates 13/32” x 1-1/2” Midget Fuse.<br />
CIRCUIT BREAKERS<br />
Thermal-Magnetic Circuit Breaker with Non-interchangeable<br />
Trip Units<br />
• 15 –600 Amperes.<br />
• 120, 240, 277, 480Y/277, 600Y/347, 690V AC 50/60Hz, 125,<br />
125/250V DC.<br />
• 1, 2 and 3 poles.<br />
Standards and Certifications<br />
Molded case circuit breakers are designed to conform with<br />
the following <strong>standard</strong>s:<br />
• Underwriters Laboratories, <strong>Inc</strong>., Standard UL489, Molded Case Circuit Breakers &<br />
Circuit Breaker Enclosures.<br />
• National Electrical Manufacturers Association Standard Publication<br />
No. AB1-1993, Molded Case Circuit Breakers.<br />
• Australian Standard AS 2184, Molded Case Circuit Breakers.<br />
• British Standards Institution Standard BS 4752: Part 1,Switchgear & Control Gear<br />
Part 1: Circuit Breakers.<br />
• Canadian Standards Association Standard C22.2 No. 5, Service Entrance & Branch<br />
Circuit Breakers.<br />
• International Electrotechnical Commission Recommendations IEC 157-1, Circuit<br />
Breakers.<br />
• Japanese T-Mark Standard Molded Case Circuit Breakers.<br />
• South African Bureau of Standards, Standard SABS 156, Standard Specification for<br />
Molded Case Circuit Breakers.<br />
• Swiss Electro-Technical Association Standard SEV 157-1, Safety<br />
Regulations for Circuit Breakers.<br />
• Union Technique de l’Electricite Switchgear & Control Gear Circuit Breaker<br />
Requirements.<br />
• Verband Deutscher Elektrotechniker (Association of German Electrical Engineers)<br />
Standard VDE 0660, Low Voltage Switchgear & Control Gear, CBs.<br />
Conformance with these <strong>standard</strong>s satisfies most local and international codes,<br />
assuming user acceptability and simplified application.<br />
Innovation<br />
New innovative design allows higher MCP-Starter combination interrupting ratings.<br />
Operator<br />
Door mounted, front rotary operating handle allows for external operation of the interior<br />
mounted motor circuit protector. The unit is pad-lockable and includes a door interlock<br />
mechanism. Available in NEMA 1, 3R, 12 and 4/4X ratings to cover a wide array of<br />
applications and environments.<br />
Molded case circuit breakers equal or exceed Federal Specification Classification<br />
W-C 475b requirements for the particular class associated with the circuit breaker<br />
frame being considered.<br />
PUSH BUTTONS<br />
Standards: IEC/EN 60947-5-1, VDE 0660,<br />
NFC63140, UL 508, UL 50, CENELEC EN50007<br />
Degree of Protection: IP66 (IEC/EN60529)<br />
UL Ratings: Type 1,2,3,3R,3S,4,4X,5,12,12K e 13<br />
Contacts Resistance: ≤ 25mΩ (IEC/EN 60255)<br />
Electrical Shock Protection: Class II<br />
Temperature Range: -25ºC to 70ºC<br />
Vibration Resistance (IEC/EN 6068-2-6): 16g with frequency<br />
range from 40 to 500HZ and max shifting 0.75mm (peak-to-peak)<br />
FUSES<br />
• Time Delay, Rejection Type Fast Acting; Branch Circuit Fuse<br />
Class CC, Class CC- Rejection Feature<br />
Voltage Rating: 600 Volts AC or Less<br />
Interrupting Rating: 200,000A RMS Sym<br />
Agency Approvals: Std. 248-4, Class CC, UL Listed, Guide JDDZ,<br />
File E4273, CSA Certified, Class 1422-01, File 53787<br />
54<br />
SPECIFICATIONS AND PRICES ARE SUBJECT TO CHANGE WITHOUT NOTICE<br />
CORDYNE, INC., 9820 DRYSDALE LN, HOUSTON, TEXAS 77041, 1-800-324-1484 OR 713-460-5151 FAX 713-460-5186 WWW.CORDYNE.COM | WWW.STORE.CORDYNE.COM<br />
COPYRIGHT © 2013 CORDYNE, INC. All Rights Reserved.