<strong>3RW3</strong> <strong>semiconductor</strong> <strong>motor</strong> <strong>control</strong> <strong>unit</strong><br />

8.3 Application and use<br />

8.3.1 Areas of application and criteria for selection<br />

The SIRIUS <strong>3RW3</strong> <strong>soft</strong> <strong>starter</strong>s offer an alternative to star-delta <strong>starter</strong>s (see<br />

Section 8.2.4 for a comparison and the advantages).<br />

The most important advantages are <strong>soft</strong> starting and <strong>soft</strong> coasting-down,<br />

interruption-free switching without current spikes that could interfere with<br />

the supply system, and compact dimensions.<br />

Many drives that needed frequency converters in the past can be changed<br />

to <strong>soft</strong>-start operation with the <strong>3RW3</strong>, if the applications do not call for variations<br />

in speed.<br />

Applications<br />

Cooling time<br />

Typical applications include, for example:<br />

Conveyor belts, conveyor systems:<br />

• Smooth starting<br />

• Smooth slowing<br />

• Use of better-value conveyor material<br />

Rotary pumps, piston-type pumps<br />

• Avoidance of pressure surges<br />

• Extended service life of the piping system<br />

Agitators, mixers:<br />

• Reduced starting current<br />

Fans:<br />

• Less strain on gearing and drive belts<br />

Note<br />

The cooling time must be taken into consideration in the starting frequency.<br />

8.3.2 Installation guidelines<br />

On account of the heat generated, certain installation guidelines must be<br />

adhered to when combining <strong>3RW3</strong>0/31 <strong>soft</strong> <strong>starter</strong>s with other SIRIUS<br />

switching devices.<br />

Stand-alone installation<br />

Stand-alone installation is when minimum vertical and lateral clearances<br />

between the mounted devices are not violated. This applies both to individual<br />

devices and complete load feeders.<br />

The following minimum clearances must be adhered to in stand-alone installation<br />

(these minimum clearances depend on the frame size):<br />

SIRIUS System Manual<br />

8-18 GWA 4NEB 430 0999-02c