<strong>3RW3</strong> <strong>semiconductor</strong> <strong>motor</strong> <strong>control</strong> <strong>unit</strong><br />

Supply interruption in<br />

bypassed state<br />

If the load voltage is switched off in the bypassed state while the auxiliary<br />

supply continues to be applied at terminals A1/A2, the <strong>soft</strong> <strong>starter</strong> performs<br />

a direct start of the <strong>motor</strong> after the load voltage is switched on again. To prevent<br />

this, the "on" command must be removed in the event of the loss of the<br />

main voltage.<br />

The following graphic illustrates what happens when the supply is interrupted<br />

in the bypassed state:<br />

L1-L2-L3<br />

A1-A2<br />

IN<br />

Bypass<br />

T1-T2-T3<br />

U N<br />

U S<br />

Direct start<br />

Control supply<br />

voltage on<br />

Main voltage<br />

on<br />

Start command<br />

Startup completed<br />

Bypass closes<br />

Failure of the<br />

main voltage<br />

Main voltage<br />

returns<br />

To avoid a direct start after the return of<br />

the main voltage, the ON command must<br />

be removed in the event of the failure<br />

failure of the main voltage (T off >= xx ms)<br />

Fig. 8-19: Supply interruption in the bypassed state<br />

SIRIUS System Manual<br />

8-34 GWA 4NEB 430 0999-02c