8.3.5 Commissioning<br />
Every SIRIUS 3RW <strong>soft</strong> <strong>starter</strong> comes with the following warning, which it is<br />
imperative to heed:<br />
Caution<br />
This device has been tested carefully at the factory and found to be in working<br />
order.<br />
During transportation, however, it may have been subject to stresses over<br />
which we have no <strong>control</strong>. The bypass relays in the main circuit may be in an<br />
undefined state.<br />
In the interests of complete safety, the following procedure should be used<br />
at commissioning or after the replacement of the SIRIUS <strong>soft</strong> <strong>starter</strong>:<br />
First, apply the supply voltage to A1/A2 in order to put the impulse series<br />
relays in a defined switching state.<br />
Then, switch on the main circuit (L1/L2/L3).<br />
If you do not do this, the <strong>motor</strong> can be switched on inadvertently and cause<br />
damage to people or parts of the system.<br />
Settings<br />
<strong>3RW3</strong>0<br />
<strong>3RW3</strong>1<br />
t R on<br />
t R1<br />
u S<br />
u S<br />
t R off<br />
t R2<br />
Fig. 8-16: Settings, <strong>3RW3</strong><br />
Note<br />
At commissioning, the settings of the potentiometers for the ramp time and<br />
the starting voltage should remain unchanged. These set values must be<br />
obtained in a trial.<br />