No. Item<br />

App.<br />

Rev.<br />

Init.<br />

Reviewer Comments<br />

Init.<br />

C-14 Do all non-<strong>residential</strong> domestic (potable)<br />

water service laterals have reduced pressure<br />

backflow devices on the customer side of<br />

the meter<br />

C-15 Domestic water service laterals cannot be<br />

run across an adjacent property line (except<br />

under certain hardship cases). Is this<br />

requirement met<br />

C-16 Each building receiving water must have at<br />

least one water service lateral, coming<br />

directly off the main line, or off of a<br />

manifolded service assembly. Is this<br />

requirement met<br />

C-17 Water service laterals cannot come off of<br />

other water service laterals. Is this<br />

requirement met<br />

C-18 On single-family residences water service<br />

laterals may be dimensioned from the<br />

property line or by street stations. Is this<br />

requirement met<br />

C-19 Are the proper types of fire hydrants<br />

installed (MCWD Std. W-8)<br />

C-20 On single family residences, water service<br />

laterals shall not go under driveway<br />

approaches. Is this requirement met<br />

C-21 Are blowoffs installed at the end of all<br />

mains <strong>and</strong> large water service stubouts<br />

They are required for testing <strong>and</strong> flushing<br />

purposes.<br />

C-22 Are air vacuum release valves installed at<br />

all water main high points for 10-inch pipe<br />

<strong>and</strong> larger<br />

C-23 Do fire hydrant spacing <strong>and</strong> coverage<br />

comply with MCWD St<strong>and</strong>ard Section 3,<br />

Fig. 1, <strong>and</strong> with the requirements of the<br />

local Fire Marshal<br />

C-24 If project is <strong>residential</strong> or medium to largescale<br />

commercial/industrial, are there at<br />

least 2 points of <strong>connection</strong> to MCWD’s<br />

water system<br />

C-25 Are all existing MCWD domestic water<br />

facilities completely <strong>and</strong> correctly depicted<br />

C-26 Are all existing <strong>and</strong> proposed points of<br />

<strong>connection</strong> to existing domestic water<br />

facilities properly depicted<br />

June 2009 A5-12