Squirrel-cage motors<br />
Technical information<br />
Converter-fed operation<br />
In general, all motors are suitable<br />
for converter-fed opera-<br />
2<br />
tion. Some motors require special<br />
measures.<br />
The planning notes for drives<br />
with a constant or square-law<br />
counter-torque are contained in<br />
the fol<strong>low</strong>ing catalogues:<br />
MICROMASTER:<br />
Catalogue series DA 64 and<br />
DA 51<br />
SIMOVERT MASTERDRIVES:<br />
Catalogue series DA 65<br />
These catalogues also contain<br />
tables showing which squirrelcage<br />
motors should be assigned<br />
to which SIMOVERT<br />
converter, depending on the<br />
load characteristic of the driven<br />
machine.<br />
■All data specified in Catalogue<br />
M11 applies to 50 Hz supply<br />
systems.<br />
Attention should be paid to the<br />
reduction factors for constanttorque<br />
drives, pump drives and<br />
compressor drives.<br />
Motor temperature detection<br />
KTY 84 temperature sensor:<br />
Order Code:<br />
A23 = 1 x KTY 84-130,<br />
A25 = 2 x KTY 84-130<br />
This sensor is a PTC thermistor.<br />
Its resistance varies as a function<br />
of the temperature in accordance<br />
with a defined curve.<br />
Some Siemens converters calculate<br />
the motor temperature<br />
according to the resistance of<br />
the temperature sensor. They<br />
can be set to a user-definable<br />
temperature for alarms and<br />
tripping.<br />
The 1LA8 motors are supplied<br />
without the standard PTC thermistor<br />
if Order Code A23 is<br />
specified.<br />
The temperature sensor is embedded<br />
in the motor winding<br />
overhang in the same way as a<br />
PTC thermistor. The evaluation<br />
is effected by the converter, for<br />
example.<br />
The 3RS10 temperature monitoring<br />
device belonging to the<br />
protection device can be ordered<br />
separately for mains-fed<br />
operation. For further details<br />
see Catalogue CA 01 Order No.<br />
E86060-D4001-A110-C1-7600.<br />
Motor protection<br />
All standard 1LA and 1LG motors<br />
for Zones 2, 21, and 22 for<br />
converter-fed operation are already<br />
fitted with a PTC thermistor<br />
for tripping. It is also possible<br />
to order a PTC thermistor<br />
for alarm for converter-fed operation<br />
(Order Code A10).<br />
Insulation<br />
The insulation of 1LA and 1LG<br />
motors is such that they can operate<br />
unrestrictedly in converter-fed<br />
mode up to <strong>voltage</strong>s of<br />
ˆ 500 V. The same applies to<br />
operation with pulse-controlled<br />
AC converters with <strong>voltage</strong> front<br />
times t s > 0.1 ms at the motor terminals.<br />
Providing these conditions are<br />
met, all motors with <strong>voltage</strong><br />
codes 1, 3, 5, and 6 can be operated<br />
in converter-fed mode,<br />
except for those with <strong>voltage</strong><br />
ratings of > 500 V to 690 V,<br />
which are supplied with special<br />
insulation for operation with a<br />
pulse-controlled AC converter<br />
(SIMOVERT MASTERDRIVES,<br />
MM440 > 500 V – 600 V) but<br />
without a converter circuit (du/dt<br />
filter or sine filter) (10th position<br />
of the Order No. = "M").<br />
For operation with a converter at<br />
the outputs specified in the catalogue,<br />
the motors are utilized<br />
according to temperature class<br />
F. Order Codes C11, C12 and<br />
C13 are not possible.<br />
Connection of the motors<br />
In addition to the restrictions applying<br />
to mains-connected machines,<br />
the maximum permissible<br />
conductor cross-sections<br />
for the converter must also be<br />
kept in mind when the motors<br />
are connected.<br />
Ventilation/<br />
noise<br />
Increased fan noise may occur<br />
in self-ventilated motors at<br />
speeds higher than the rated<br />
speed.<br />
To increase motor utilization for<br />
<strong>low</strong> speeds, it is advisable to<br />
use separately ventilated motors<br />
such as 1LA5, 1LA7, 1LG,<br />
and 1LG6 with Order Code G17<br />
or motor 1PQ8.<br />
Mechanical stress, grease life<br />
Due to the higher speeds beyond<br />
the rated speed value and<br />
the resulting increased vibration,<br />
the mechanical balance<br />
quality changes and the bearings<br />
are under greater mechanical<br />
stress. This reduces the<br />
grease life and the bearing life.<br />
(enquire if necessary).<br />
Bearings<br />
To avoid damage by bearing<br />
currents, isolated bearings for<br />
frame sizes 225 to 315 are available<br />
and recommended for<br />
frame size 280 (Order Code<br />
L27) 1 ). These are standard in<br />
1LA8 motors for converter-fed<br />
operation on SIMOVERT<br />
MASTERDRIVES (9 th position<br />
of the Order No. = "P").<br />
3<br />
M1-5178<br />
R<br />
2<br />
k<br />
1<br />
D = 2 mA<br />
0<br />
0<br />
100<br />
°C<br />
200<br />
T U<br />
300<br />
1) For 1MJ7 motors, Order Code<br />
L27 can be used for frame sizes<br />
250 to 315.<br />
2/44<br />
Siemens M 11 · 2003/2004