arc-flash analysis of utility power systems - Michigan Technological ...
arc-flash analysis of utility power systems - Michigan Technological ...
arc-flash analysis of utility power systems - Michigan Technological ...
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Bus Voltage<br />
(kV)<br />
Table 4.1: 1 kV voltage level test system incident energy values<br />
Incident Energy (cal/cm 2 )<br />
Based on Bus<br />
Voltage<br />
Empirical Equation Lee Equation<br />
0.5 109.89 1311.72 109.89<br />
0.6 173.60 1112.42 173.60<br />
0.7 274.65 966.29 274.65<br />
0.8 433.71 852.72 433.71<br />
0.9 683.28 761.94 683.28<br />
1 1074.61 688.33 688.33<br />
1.1 1688.36 628.00 628.00<br />
1.2 2651.74 578.13 578.13<br />
1.3 4167.63 536.78 536.78<br />
1.4 6558.29 502.31 502.31<br />
1.5 10345.38 473.69 473.69<br />
Table 4.2: 15 kV voltage level test system incident energy values<br />
Bus Voltage<br />
(kV)<br />
Incident Energy (cal/cm 2 )<br />
Based on Bus<br />
Voltage<br />
Empirical Equation Lee Equation<br />
14.0 0.94 21.50 0.94<br />
14.1 0.94 21.81 0.94<br />
14.2 0.95 22.12 0.95<br />
14.3 0.96 22.43 0.96<br />
14.4 0.96 22.75 0.96<br />
14.5 0.97 23.07 0.97<br />
14.6 0.98 23.38 0.98<br />
14.7 0.99 23.70 0.99<br />
14.8 0.99 24.03 0.99<br />
14.9 1.00 24.36 1.00<br />
15.0 1.01 24.68 1.01<br />
15.1 1.01 25.01 25.01<br />
15.2 1.02 25.34 25.34<br />
15.3 1.03 25.68 25.68<br />
15.4 1.04 26.02 26.02<br />
15.5 1.04 26.35 26.35<br />
15.6 1.05 26.69 26.69<br />
15.7 1.06 27.04 27.04<br />
15.8 1.06 27.38 27.38<br />
15.9 1.07 27.73 27.73<br />
16.0 1.08 28.08 28.08<br />
This is especially concerning due to the fact the NESC does not specify at what<br />
conditions the <strong>analysis</strong> is to be conducted; i.e. under light load or peak load conditions.<br />
32