01.02.2015 Views

arc-flash analysis of utility power systems - Michigan Technological ...

arc-flash analysis of utility power systems - Michigan Technological ...

arc-flash analysis of utility power systems - Michigan Technological ...

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

If we refer to Figure 4.2 were we have two radial feeders connected to the<br />

system. In our case the load at bus 2 is 350 amps and bus 3 is 100 amps giving a total<br />

current at bus 1 to be 450 amps. Since bus 1 is the closest to the system it will have<br />

the highest fault current available with bus 2 being the second largest and bus 3 is the<br />

lowest on the feeder. When using inverse time overcurrent curves like those in Figure<br />

4.6 and applying them to the fault currents on each bus down the feeder, we see that<br />

the largest incident energy will be at bus 1 and reduces as we move down the feeder<br />

towards bus 3 in the same fashion as Figure 4.8 depicts.<br />

If a 50/51 relay was to be used instead <strong>of</strong> just a 51 relay, then the feeder would<br />

have two points where the incident energy would need to be calculated; one at the<br />

feeder source and one at the position were the 50 relay would stop operating and the<br />

51 relay would start operating.<br />

36

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!