arc-flash analysis of utility power systems - Michigan Technological ...
arc-flash analysis of utility power systems - Michigan Technological ...
arc-flash analysis of utility power systems - Michigan Technological ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
If we refer to Figure 4.2 were we have two radial feeders connected to the<br />
system. In our case the load at bus 2 is 350 amps and bus 3 is 100 amps giving a total<br />
current at bus 1 to be 450 amps. Since bus 1 is the closest to the system it will have<br />
the highest fault current available with bus 2 being the second largest and bus 3 is the<br />
lowest on the feeder. When using inverse time overcurrent curves like those in Figure<br />
4.6 and applying them to the fault currents on each bus down the feeder, we see that<br />
the largest incident energy will be at bus 1 and reduces as we move down the feeder<br />
towards bus 3 in the same fashion as Figure 4.8 depicts.<br />
If a 50/51 relay was to be used instead <strong>of</strong> just a 51 relay, then the feeder would<br />
have two points where the incident energy would need to be calculated; one at the<br />
feeder source and one at the position were the 50 relay would stop operating and the<br />
51 relay would start operating.<br />
36