Pump Capacity 5,6<br />
70<br />
60<br />
50<br />
A<br />
Pressure (psi)<br />
40<br />
30<br />
20<br />
10<br />
D<br />
C<br />
B<br />
E<br />
F<br />
A=TU-7, 60Hz<br />
B=TU-7, 50Hz<br />
C=TU-3, 60Hz<br />
D=TU-3, 50Hz<br />
E=CP-55, 60Hz<br />
F=CP-55, 50HZ<br />
5 10 15 20<br />
Flow (gallons/minute)<br />
5.TU-7, TU-8, and TU-9 pumps require 3Ø power.<br />
6.TU-5 pumps are rated 9 gpm @ 50 psi, TU-6 pumps are 12 gpm @ 50 psi, TU-8 pumps<br />
are 20 gpm @ 50 psi, and TU-9 pumps 23 gpm @ 50 psi.<br />