14.03.2015 Views

EA New Homes Measures Guide - Earth Advantage

EA New Homes Measures Guide - Earth Advantage

EA New Homes Measures Guide - Earth Advantage

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

2012 <strong>Earth</strong> <strong>Advantage</strong> Residential<br />

<strong>Measures</strong> Resource <strong>Guide</strong><br />

5.1.3<br />

Balanced System - Exhaust and supply balanced w/o heat recovery.<br />

Energy<br />

Materials<br />

Water<br />

0 2 0 1 0<br />

Description: There are several different ways to create a balanced ventilation system without heat recovery. In all cases, exhaust fans<br />

installed in the living area must be ENERGY STAR labeled. Remote-mounted fans in attics, crawlspaces, garages do not require ENERGY<br />

STAR labels, but should be selected for low-energy, quiet operation. <br />

<br />

Option 1: Using an inline supply air fan and a branched duct system to DELIVER fresh air to multiple locations (typically bedrooms.) A<br />

single exhaust fan shall be wired to the same circuit to operate simultaneously with the supply fan. A 24 hour programmable timer must<br />

control the system to meet ASHRAE 62.2 <br />

<br />

Option 2: Using an inline exhaust fan and a branched duct system to REMOVE stale air from multiple locations (typically bathrooms,<br />

laundry or kitchen.) A single low sone inline supply fan shall be wired to the same circuit to operate simultaneously with the exhaust fan.<br />

A 24 hour programmable timer must control the system to meet ASHRAE 62.2 <br />

<br />

Option 3: An integrated exhaust system with multiple exhaust fans plus a passive supply air duct with a mechanically controlled damper.<br />

The supply air duct may connect to the air handler or be the through wall type. The system must have a common controller which can<br />

coordinate the fans with the opening of the supply air duct. The controller must also be programmable to meet ASHRAE 62.2. <br />

<br />

Option 4: In homes with forced air heating systems, a single exhaust fan and a fresh air duct to the air handler are wired to the same<br />

control. This operates the exhaust and supply at the same time to provide balanced ventilation. <br />

<br />

Option 5: An exhaust fan with adjustable air flow rate set to ASHRAE 62.2 runs continuously. A supply duct is connected to the air handler<br />

on the return side with a manual damper installed. The damper shall be adjusted so that the flow rate is set to ASHRAE 62.2 when the air<br />

handler is running at high speed. <br />

<br />

Option 6: An exhaust fan is installed in a central location. A supply duct is connected to the air handler on the return side with a motorized<br />

damper installed. An adjustable damper is set to allow the air flow rate to be set to ASHRAE 62.2. The exhaust fan, motorized damper and<br />

furnace blower are all connected to the same 24-hour timer set to run 10 minutes each hour.<br />

Health<br />

Land<br />

Benefit: This fresh air ventilation system removes stale indoor air and also supplies fresh outdoor air. This improves the indoor air quality<br />

of the home. This system can improve the indoor air quality of the house by mixing fresh air from outside. Balancing supply and exhaust<br />

provides better ventilation while reducing the potential for pressure imbalance inside the home.<br />

Verification: <strong>EA</strong> Rater will engage the system to ensure that the exhaust and supply are operating simultaneously. Rater will verify the<br />

Supply air is routed from outdoor sidewalls, gable end wall, or soffit vent (with sealed ductwork to the exterior so no attic air can be drawn<br />

in.)<br />

5.1.4<br />

Spot HRV/ERV<br />

Energy<br />

Materials<br />

Water<br />

0 2 0 1 0<br />

Description: One spot HRV/ERV per approximately 1000 sq ft is required in order to have sufficient ventilation capacity. HRVs and ERVs<br />

typically operate continuously on a low speed. Some have the ability to boost flow when more ventilation is needed. These may be used in<br />

place of local ventilation in bathrooms, provided they deliver enough ventilation at high speed to meet local ventilation requirements.<br />

Health<br />

Land<br />

Benefit: HRVs and ERVs are considered the premium ventilation systems. They are highly effective and reduce the energy penalty<br />

associated with all fresh air ventilation. By tempering incoming air, these units provide greater comfort in extreme climates than other<br />

types of ventilation systems.<br />

Verification: <strong>EA</strong> Rater will engage the system to ensure that the exhaust and supply are operating simultaneously. Rater will verify the<br />

Supply air is routed from outdoor sidewalls, gable end wall, or soffit vent (with sealed ductwork to the exterior so no attic air can be drawn<br />

in.)<br />

Page 41 of 70

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!