Installation positions<br />

The circuit-breaker can be installed in any position without any<br />

effect on its rated characteristics. In <strong>com</strong>pliance with the IEC<br />

60947-2 Standards, SACE Isomax S circuit-breakers can be<br />

supplied through either top or bottom terminals, without jeopardising<br />

operation of the apparatus.<br />

They can be installed in switchboards, mounted directly on the<br />

base plate or on Din rails up to size S5.<br />

GSIS9131 GSIS9128<br />

Mounting on DIN rail up to 630 A<br />

The brackets for fixing onto standardised DIN EN 50022 rails<br />

for S1, S2 and DIN EN 50023 rails for S3, S4, S5 simplify assembly<br />

of the circuit-breakers up to 630 A in standard switchboards.<br />

This allows standardised supporting structures to be used and<br />

facilitates the stage for designing and constructing the switchboard<br />

metalwork structure.<br />

GSIS9130 GSIS9062<br />

2<br />

Resistance to vibration<br />

Degrees of protection<br />

The circuit-breakers are unaffected by vibrations generated<br />

mechanically or due to electromagnetic effects, in <strong>com</strong>pliance<br />

with the IEC 68-2-6 Standards and the strictest regulations of<br />

the major classification organisations:<br />

– RINA<br />

– DET Norske Veritas<br />

– Lloyd’s Register of Shipping<br />

– Germanischer Lloyd<br />

– Bureau Veritas.<br />

Different measures have been taken in SACE Isomax S circuitbreakers<br />

to achieve IP20 degree of protection for the fixed,<br />

plug-in and withdrawable version circuit-breaker, excluding<br />

the terminals, and IP30 for the front parts of the circuit-breakers<br />

installed in switchboards.<br />

The fixed parts are always provided with IP20 degree of protection.<br />

It is possible to achieve IP54 degree of protection in accordance<br />

with the IEC 60529 Standard with the circuit-breaker<br />

installed in a switchboard fitted with rotary handle operating<br />

mechanism transmission on the <strong>com</strong>partment door and the<br />

special insulation gaskets which can be ordered separately.<br />