SACE Isomax S circuit-breakers for power<br />
distribution<br />
Electronic releases<br />
The SACE Isomax S4, S5, S6, S7 and S8 circuit-breakers for protection in alternating<br />
current can be fitted with SACE PR211/P or SACE PR212/P overcurrent releases,<br />
constructed using electronic microprocessor-based technology. This allows protection<br />
functions to be obtained which guarantee a high level of reliability and tripping<br />
precision and which are unaffected by the external ambient. The power supply<br />
needed for correct operation is supplied directly by the release current transformers,<br />
in the presence of a phase current higher than or equal to 18% of their rated current,<br />
even with a single phase supplied with voltage. There is only one adjustment for all<br />
the phases and the neutral and the release is simultaneous for all the circuit-breaker<br />
poles, with trip characteristics which are unaffected by the external ambient. The<br />
functions and settings of the release protections can be verified by means of the<br />
SACE TT1 and SACE PR010/T Test units.<br />
GSIS9060<br />
SACE PR211/P<br />
SACE PR212/P<br />
3<br />
The SACE PR211/P release (available<br />
from S4 to S7) provides protection functions<br />
against overload L and instantaneous<br />
short-circuit I, and is available in<br />
the versions with functions I and LI.<br />
The wide range of adjustments make this<br />
release particularly suitable in all distribution<br />
where tripping reliability and precision<br />
is required and where magnetic<br />
only protection is needed (from 1.5 to<br />
12 x In), using the SACE PR211/P version<br />
I release.<br />
The SACE PR212/P release (available<br />
from S4 to S8) provides protection functions<br />
against overload L, delayed shortcircuit<br />
S and instantaneous short-circuit<br />
I, and against earth fault G. It is available<br />
in the versions PR212/P with functions<br />
LSI and LSIG; both allow use of the<br />
PR010/K signalling unit, the PR212/D<br />
dialogue unit and the PR212/T actuator<br />
unit, which can be used either simultaneously<br />
or individually, except for the<br />
PR212/T actuator unit which is always<br />
supplied when the dialogue unit is required.<br />
It is particularly suitable in applications<br />
with selective coordination requirements,<br />
for earthing protection against the<br />
risk of fire and evolutionary faults, and<br />
for remote control and parametrisation,<br />
network supervision and centralised<br />
load management.<br />
In 100 A 160 A 250 A 320 A<br />
S4 160<br />
S4 250<br />
S5 400<br />
S5 630<br />
S6 630<br />
S6 800<br />
S7 1250<br />
S7 1600<br />
S8 2000<br />
S8 2500<br />
S8 3200<br />
L 40÷100 64÷160 100÷250 128÷320<br />
S 100÷1000 160÷1600 250÷2500 320÷3200<br />
I 150÷1200 240÷1920 375÷3000 480÷3840<br />
G 20÷100 32÷160 50÷250 64÷320<br />
neutral (50%)<br />
neutral (100%)<br />
20÷50 32÷80 50÷125 64÷160<br />
40÷100 64÷160 100÷250 128÷320<br />
3/10 ABB SACE