SACE Isomax S circuit-breakers for power<br />

distribution<br />

Electronic releases<br />

The SACE Isomax S4, S5, S6, S7 and S8 circuit-breakers for protection in alternating<br />

current can be fitted with SACE PR211/P or SACE PR212/P overcurrent releases,<br />

constructed using electronic microprocessor-based technology. This allows protection<br />

functions to be obtained which guarantee a high level of reliability and tripping<br />

precision and which are unaffected by the external ambient. The power supply<br />

needed for correct operation is supplied directly by the release current transformers,<br />

in the presence of a phase current higher than or equal to 18% of their rated current,<br />

even with a single phase supplied with voltage. There is only one adjustment for all<br />

the phases and the neutral and the release is simultaneous for all the circuit-breaker<br />

poles, with trip characteristics which are unaffected by the external ambient. The<br />

functions and settings of the release protections can be verified by means of the<br />

SACE TT1 and SACE PR010/T Test units.<br />

GSIS9060<br />

SACE PR211/P<br />

SACE PR212/P<br />

3<br />

The SACE PR211/P release (available<br />

from S4 to S7) provides protection functions<br />

against overload L and instantaneous<br />

short-circuit I, and is available in<br />

the versions with functions I and LI.<br />

The wide range of adjustments make this<br />

release particularly suitable in all distribution<br />

where tripping reliability and precision<br />

is required and where magnetic<br />

only protection is needed (from 1.5 to<br />

12 x In), using the SACE PR211/P version<br />

I release.<br />

The SACE PR212/P release (available<br />

from S4 to S8) provides protection functions<br />

against overload L, delayed shortcircuit<br />

S and instantaneous short-circuit<br />

I, and against earth fault G. It is available<br />

in the versions PR212/P with functions<br />

LSI and LSIG; both allow use of the<br />

PR010/K signalling unit, the PR212/D<br />

dialogue unit and the PR212/T actuator<br />

unit, which can be used either simultaneously<br />

or individually, except for the<br />

PR212/T actuator unit which is always<br />

supplied when the dialogue unit is required.<br />

It is particularly suitable in applications<br />

with selective coordination requirements,<br />

for earthing protection against the<br />

risk of fire and evolutionary faults, and<br />

for remote control and parametrisation,<br />

network supervision and centralised<br />

load management.<br />

In 100 A 160 A 250 A 320 A<br />

S4 160<br />

S4 250<br />

S5 400<br />

S5 630<br />

S6 630<br />

S6 800<br />

S7 1250<br />

S7 1600<br />

S8 2000<br />

S8 2500<br />

S8 3200<br />

L 40÷100 64÷160 100÷250 128÷320<br />

S 100÷1000 160÷1600 250÷2500 320÷3200<br />

I 150÷1200 240÷1920 375÷3000 480÷3840<br />

G 20÷100 32÷160 50÷250 64÷320<br />

neutral (50%)<br />

neutral (100%)<br />

20÷50 32÷80 50÷125 64÷160<br />

40÷100 64÷160 100÷250 128÷320<br />

3/10 ABB SACE