SACE Isomax S circuit-breakers<br />

for power distribution<br />

Electronic releases<br />

Protection functions and parametrisation of the SACE PR211/P, PR212/P releases<br />

Protection function<br />

Trip threshold<br />

CANNOT<br />

BE EXCLUDED<br />

Against overload with inverse long time<br />

delay and trip characteristic according to<br />

a time dependent curve (I 2 t = constant)<br />

I1 = 0,4 - 0,5 - 0,6 - 0,7 - 0,8 - 0,95 - 1 x In PR211/P (I - LI)<br />

I1 = 0,4 - 0,5 - 0,55 - 0,6 - 0,65 - 0,7 - 0,75 - 0,8 - 0,85 - 0,875 -<br />

0,9 - 0,925 - 0,95 - 0,975 - 1 x In PR212/P (LSI - LSIG)<br />

Release between 1,05 ... 1,30 x I1 (IEC 60947-2)<br />

CAN<br />

BE EXCLUDED<br />

Against short-circuit with inverse short<br />

time delay and trip characteristic with<br />

dependent time (I 2 t = constant) or<br />

independent time<br />

I 2 t=cost<br />

ON<br />

I 2 t=cost<br />

OFF<br />

I2 = 1 - 2 - 3 - 4 - 6 - 8 - 10 x In<br />

Tolerance + 10%<br />

I2 = 1 - 2 - 3 - 4 - 6 - 8 - 10 x In<br />

Tolerance + 10%<br />

CAN<br />

BE EXCLUDED<br />

Against short-circuit with adjustable<br />

instantaneous trip<br />

I3 = 1,5 - 2 - 4 - 6 - 8 - 10 - 12 x In (*)<br />

Tolerance + 20%<br />

(*) For S5 630, I3 max = 8 x In<br />

3<br />

CAN<br />

BE EXCLUDED<br />

Against earth fault with short inverse<br />

time delay and trip characteristic<br />

according to a dependent time curve<br />

(I 2 t = constant)<br />

I4 = 0,2 - 0,3 -0,4 - 0,6 - 0,8 - 0,9 - 1xIn<br />

Tolerance + 20%<br />

SACE PR211/P electronic release, functions I or LI<br />

Protection L<br />

Against overload<br />

Protection I<br />

Against short-circuit with<br />

instantaneous trip<br />

Socket for Test<br />

SACE TT1 Test unit<br />

GSIS9054<br />

3/12 ABB SACE