Electronic overcurrent releases<br />

SACE PR211/P - PR212/P electronic overcurrent releases<br />

Circuit-breaker Release L1 - L2 - L3 phases Neutral Neutral ( 1 )<br />

S4X 250 S6X 400 S6X 630 current L S I G (50% Ith) (100% Ith)<br />

In [A] I1 [A] I2 [A] I3 [A] I4 [A] [A] [A]<br />

100 40 ... 100 100 ... 1000 150 ... 1200 20 ... 100 20 ... 50 40 ... 100<br />

160 64 ... 160 160 ... 1600 240 ... 1920 32 ... 160 32 ... 80 64 ... 160<br />

250 100 ... 250 250 ... 2500 375 ... 3000 50 ... 250 50 ... 125 100 ... 250<br />

320 128 ... 320 320 ... 3200 480 ... 3840 64 ... 320 64 ... 160 128 ... 320<br />

400 160 ... 400 400 ... 4000 600 ... 4800 80 ... 400 80 ... 200 160 ... 400<br />

630 252 ... 630 630 ... 6300 945 ... 7560 126 ... 630 126 ... 315 252 ... 630<br />

L = Protection function against overload<br />

S = Protection function against short-circuit with delayed trip<br />

I = Protection function against short-circuit with instantaneous trip<br />

G = Protection function against earth fault with delayed trip<br />

( 1 ) Only for PR212/P. Available on request for PR211/P, with additional ordering code 1SDA037505R1.<br />

N.B. For more detailed information about the protection functions, please see page 3/12.<br />

3<br />

GSIS9115<br />

SACE S4X, S6X circuit-breakers, with microprocessorbased<br />

overcurrent releases<br />

ABB SACE<br />

3/21