INDUSTRIAL INDEXING SYSTEMS, Inc.<br />

EMERALD SERIES MOTORS & DRIVES<br />

5.2 MAIN BUS POWER SUPPLY WIRING<br />

IB-21B001<br />

USER’S GUIDE<br />

Connect the <strong>Emerald</strong> drive main bus power (L1, L2, L3) to the incoming line or transformer (See Section<br />

4.1.2 & Section 5.2.4). Section 5.2.3 details the required wiring to maintain the NRTL Certification. It is<br />

important that the recommended components or equivalent components with NRTL approval be included<br />

in system design. See Figure 5.1 for the required power wiring connections.<br />

5.2.1 SUPPLEMENTAL CIRCUIT PROTECTION<br />

It is required that each driver/motor combination be provided with a circuit protector for each driver and<br />

motor pair. All of the drives are suitable for use on a circuit capable of delivering not more than 5000 rms<br />

symmetrical amperes.<br />

<strong>Drive</strong> Part No.<br />

ESD-5/AEP<br />

(single phase)<br />

ESD-5/AEP<br />

(single phase)<br />

ESD-5/AEP<br />

(3-Phase)<br />

ESD-10/AEP<br />

(3-Phase)<br />

ESD-20/AEP<br />

(3-Phase)<br />

ESD-25/CEP<br />

(3-Phase)<br />

ESD-40/AEP<br />

(3-Phase)<br />

ESD-50/CEP<br />

(3-Phase)<br />

ESD-60/AEP<br />

(3-Phase)<br />

Motor Rated<br />

Current<br />

(Amps)<br />

Edison MEQ<br />

FUSE<br />

Rating<br />

Circuit Protectors<br />

Edison Rating<br />

JDL FUSE<br />

Edison<br />

CIRCUIT<br />

BREAKER<br />

Rating<br />

1.7A to 3.4A MEQ5 5A JDL5 5A ---- ----<br />

3.4A and up MEQ10 10A JDL10 10A ---- ----<br />

1.7A and up MEQ5 5A JDL5 5A ---- ----<br />

3.4A and up MEQ10 10A JDL10 10A ---- ----<br />

6.7A and up MEQ20 20A JDL20 20A G3P-020 20A<br />

8.4A and up ---- ---- JDL25 25A G3P-025 25A<br />

13.4A and up ---- ---- JDL40 40A G3P-040 40A<br />

16.7A and up ---- ---- JDL50 50A G3P-050 50A<br />

20.0A and up ---- ---- JDL60 60A G3P-060 60A<br />

Table 5.1 - Recommended Circuit Protector<br />

The circuit protector is sized for the worst-case maximum power draw of the driver at the worst-case low<br />

line voltage. The chart contains specific vendor and size recommendations. Other types of circuit<br />

protectors or fuses may be used provided the continuous ratings are equivalent, the instantaneous rating<br />

is 10 to 15 times continuous and can support 3 times continuous for at least 3 seconds. Contact<br />

<strong>Industrial</strong> <strong>Indexing</strong> <strong>Systems</strong>, Inc. for specific recommendations of circuit protective devices.<br />

NOTE: All drive sizes can be run on single-phase AC input. However with the exception of the ESD-<br />

5/XXX drive, all other drives will have their capabilities reduced by up to 50%. <strong>Industrial</strong> <strong>Indexing</strong><br />

<strong>Systems</strong>, Inc. does not recommend running any drive with the exception of the ESD-5/XXX with a singlephase<br />

AC input.<br />

APRIL 2008 PAGE 5 - 2