CHAPTER-2<br />

EIA/EMP OF Shree Shakambari Ferro Alloys <strong>Pvt</strong>. <strong>Ltd</strong>.<br />

shall be interconnected, as per IEEE:80 recommendations & IS:3043. Non-current<br />

carrying parts of all electrical equipments viz., motors, MCCs, PCCs, distribution<br />

boards, control panels, HT switchgears, generators and all lightning fittings shall<br />

also be earthed rigidity to ensure safety.<br />

Cables:<br />

All cables shall be selected to carry the load current under site conditions, with<br />

permissible voltage drop. In addition, high voltage cables shall be sized to<br />

withstand the short circuit current. The following types of cables shall be used.<br />

Power cables for 11 Kv system will be with three core aluminium conductor,<br />

XLPE insulated, screened, armoured and overall PVC sheathed confirming to<br />

IS:7098/IEC:502<br />

The power cables of 1.1 Kv grade will be PVC insulated, aluminum conductor,<br />

inner sheath PVC taped strip/wire armoured with outer sheath of PVC<br />

compound conforming.<br />

The control cables for control/protection/indication circuit of the various<br />

equipment will be of 1.1 Kv grade, PVC insulated annealed high conductivity<br />

stranded copper conductor, inner sheath PVC taped, flat/ round wire armoured<br />

with outer sheathe of PVC compound conforming to latest.<br />

AC Auxiliary Supply:<br />

AC supplies of single and three phase, needed for internal use for several<br />

functions such as Illumination, Battery charging, UPS, Transformers tapchanger<br />

drives, Excitation supply, Power supplies for communication equipment,<br />

Breakers/Disconnect switch motors, space heaters in cubicles, generators and<br />

marshaling kiosis shall be arranged from minimum two supply sources.<br />

ECOMEN LABORATORIES PVT.LTD., LUCKNOW