7. External Static Pressure (E.S.P) & Air FlowURNU07GB1G1, URNU09GB1G1, URNU12GB1G1, URNU15GB1G1(Unit: CMM)Ceiling Concealed Duct- Low StaticSetting ValueStatic Pressure(mmAq(Pa))0(0) 1(10) 2(20) 3(29) 4(39)60 6.02 2.25 0.61 - -65 6.95 3.32 0.73 0.54 0.4870 7.69 5.16 1.19 0.65 0.5675 8.46 6.93 2.42 0.77 0.6380 9.5 7.37 3.4 0.87 0.7285 10.35 8.72 5.33 1.35 0.8890 10.81 9.66 6.75 3.15 0.9895 11.57 10.31 8.56 4.73 1.03100 12.58 11.22 9.75 7.46 2.31105 13.31 12.27 10.89 8.64 5.01110 14.2 13.24 12.15 10.49 7.7115 14.82 13.92 12.64 11.16 9.48URNU18GB2G1, URNU24GB2G1(Unit: CMM)Setting ValueStatic Pressure(mmAq(Pa))0(0) 1(10) 2(20) 3(29) 4(39)65 10.07 6.9 0.82 - -70 11.39 8.49 2.2 - -75 12.01 9.79 4.2 - -80 13.21 11.03 5.92 0.92 -85 14.24 12.36 9.41 2.1 -90 15.04 13.34 10.8 5.29 1.0195 16.02 14.63 12.5 7.59 1.34100 17.11 15.56 13.66 11.53 5.35105 17.99 16.53 15.17 12.35 7.67110 19.04 17.71 16.22 14.23 10.45115 19.77 18.62 17.1 15.23 13.25120 20.94 19.92 18.56 16.98 14.66125 21.97 20.56 19.25 17.68 16.06130 22.83 21.98 20.75 19.32 17.73Note :1. The above table shows the correlation between the air rates and E.S.P.5-11<strong>Indoor</strong> <strong>unit</strong>Ceiling Concealed Duct- Low Static