8. Electric CharacteristicsCassette 1-wayUnitsPower Supply IFM Input(W)Model Type Hz Volts Voltage Range MCA MFA kW FLA Cooling HeatingARNU07GTJ*2TJ1.29 15 0.02 0.23 40 40Max:264ARNU09GTJ*2 TJ 50 220~2401.29 15 0.02 0.23 40 40Min:198ARNU12GTJ*2 TJ 1.29 15 0.02 0.23 40 40ARNU07GTJ*2TJ1.29 15 0.02 0.23 40 40Max:242ARNU09GTJ*2 TJ 60 2201.29 15 0.02 0.23 40 40Min:198ARNU12GTJ*2 TJ 1.29 15 0.02 0.23 40 40Symbols:MCA : Minimum Circuit Amperes (A)MFA : Maximum Fuse Amperes(see note 5)kW : Fan Motor Rated Output(kW)FLA : Full Load Amperes(A)IFM : <strong>Indoor</strong> Fan MotorNote :1. Voltage RangeUnits are suitable for use on electrical system where voltage supplied to <strong>unit</strong> terminals is not below or above thelisted range limits.2. Maximum allowable voltage unbalance between phase is 2%.3. MCA/MFAMCA = 1.25 x FLA + 1MFA ≤ 4 x FLA( Next lower standard fuse rating. Minimum 15A)4. Select wire size based on the larger value on the MCA.5. Instead of fuse, use Circuit Breaker.1-10<strong>Indoor</strong> <strong>unit</strong>Ceiling Cassette 1-way