8. Electric CharacteristicsUnitsPower Supply IFM Input(W)Model Type Hz Volts Voltage Range MCA MFA kW FLA Cooling HeatingARNU07GSE*2 SE 1.29 15 0.02 0.23 40 40ARNU09GSE*2 SE 1.29 15 0.02 0.23 40 40ARNU12GSE*2 SEMax:264 1.29 15 0.02 0.23 40 4050 220 ~ 240ARNU15GSE*2 SE Min:198 1.29 15 0.02 0.23 40 40ARNU18GS3*2 S3 1.29 15 0.02 0.23 40 40ARNU24GS3*2 S3 1.29 15 0.02 0.23 40 40ARNU07GSE*2 SE 1.29 15 0.02 0.23 40 40ARNU09GSE*2 SE 1.29 15 0.02 0.23 40 40ARNU12GSE*2 SEMax:242 1.29 15 0.02 0.23 40 4060 220ARNU15GSE*2 SE Min:198 1.29 15 0.02 0.23 40 40ARNU18GS3*2 S3 1.29 15 0.02 0.23 40 40ARNU24GS3*2 S3 1.29 15 0.02 0.23 40 40ART COOL MirrorSymbols:MCA : Minimum Circuit Amperes (A)MFA : Maximum Fuse Amperes(see note 5)kW : Fan Motor Rated Output(kW)FLA : Full Load Amperes(A)IFM : <strong>Indoor</strong> Fan MotorNote :1. Voltage RangeUnits are suitable for use on electrical system where voltage supplied to <strong>unit</strong> terminals is not below or above thelisted range limits.2. Maximum allowable voltage unbalance between phase is 2%.3. MCA/MFAMCA = 1.25 x FLA + 1MFA ≤ 4 x FLA( Next lower standard fuse rating. Minimum 15A)4. Select wire size based on the MCA.ART COOL Mirror <strong>Indoor</strong> <strong>unit</strong>8-14