You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

8. Electric CharacteristicsUnitsPower Supply IFM Input(W)Model Type Hz Volts Voltage Range MCA MFA kW FLA Cooling HeatingARNU07GSE*2 SE 1.29 15 0.02 0.23 40 40ARNU09GSE*2 SE 1.29 15 0.02 0.23 40 40ARNU12GSE*2SEMax:264 1.29 15 0.02 0.23 40 4050 220 ~ 240ARNU15GSE*2 SE Min:198 1.29 15 0.02 0.23 40 40ARNU18GS5*2 S5 1.29 15 0.02 0.23 40 40ARNU24GS5*2 S5 1.29 15 0.02 0.23 40 40ARNU07GSE*2 SE 1.29 15 0.02 0.23 40 40ARNU09GSE*2 SE 1.29 15 0.02 0.23 40 40ARNU12GSE*2SEMax:242 1.29 15 0.02 0.23 40 4060 220ARNU15GSE*2 SE Min:198 1.29 15 0.02 0.23 40 40ARNU18GS5*2 S5 1.29 15 0.02 0.23 40 40ARNU24GS5*2 S5 1.29 15 0.02 0.23 40 40Wall MountedSymbols:MCA :Min, Circuit Amps(A)MFA:Max. Fuse Amps(see note 5)kW:Fan Motor Rated Output(kW)FLA:Full Load Amps(A)IFM:<strong>Indoor</strong> Fan MotorNote :1. Voltage rangeUnits are suitable for use on electrical systems where voltage supplied to <strong>unit</strong> terminals is not below or abovethe listed range limits.2. Maximum allowable voltage unbalance between phases is 2%3. MCA/MFAMCA=1.25 x FLA + 1MFA≤ 4 x FLA(Next lower standard fuse rating. Min. 15A)4. Select wire size based on the MCA5. Instead of fuse, use Circuit Breaker.Wall Mounted <strong>Indoor</strong> <strong>unit</strong>7-14