8-7. HOW TO CHECK THE PARTSPLA-RP3AA.UKPLA-RP4AA.UKPLA-RP5AA.UKPLA-RP6AA.UKParts nameRoom temperaturethermistor (TH1)Pipe temperaturethermistor (TH2)Condenser/Evaporatortemperature thermistor(TH5)Vane motorCheck pointsDisconnect the connector then measure the resistance using a tester.(Surrounding temperature 10:~30:)Normal4.3k"~9.6k"AbnormalOpen or shortMeasure the resistance between the terminals using a tester.(Surrounding temperature20:)NormalAbnormal15k" Open or short(Refer to the thermistor)Fan motorDrain pumpRelay connector123RedWhiteBlack123ProtectorOFF:130:ON :80i20:Measure the resistance between the terminals using a tester.(Winding temperature 20:)Motor terminalorRelay connectorRed-BlackWhite-BlackPLA-RP3AA.UK87.2"104.1"NormalPLA-RP4,5,6AA.UK28.7"41.6"Measure the resistance between the terminals using a tester.(Winding temperature 20:)AbnormalOpen or shortRedRedDrain sensor12123NormalAbnormal290" Open or shortMeasure the resistance between the terminals using a tester.Measure the resistance after 3 minutes have passed since the power supply was intercepted.(Surrounding temperature 0:~60:)Normal0.6k"~6.0k"AbnormalOpen or short(Refer to the thermistor)35