Table 26, WGS 130AA – 190AA, Remote Condenser,Wiring to Multiple-Point Disconnect SwitchWGSUNITSIZE130AA140AA160AA170AA190AAWIRING TO UNIT DISCONNECT SWITCHVOLTSTERMINAL SIZE CONNECTOR WIRE RANGE PER PHASE(AMPS)(COPPER WIRE ONLY)CKT 1 CKT 2 CKT 1 CKT 2208 400 400 3/0-500 3/0-500230 400 400 3/0-500 3/0-500380 250 250 #6-350 #6-350460 250 250 #6-350 #6-350575 250 250 #6-350 #6-350208 400 400 3/0-500 3/0-500230 400 400 3/0-500 3/0-500380 250 250 #6-350 #6-350460 250 250 #6-350 #6-350575 250 250 #6-350 #6-350208 400 400 3/0-500 3/0-500230 400 400 3/0-500 3/0-500380 250 250 #6-350 #6-350460 250 250 #6-350 #6-350575 250 250 #6-350 #6-350208 400 400 3/0-500 3/0-500230 400 400 3/0-500 3/0-500380 250 250 #6-350 #6-350460 250 250 #6-350 #6-350575 250 250 #6-350 #6-350208 400 400 3/0-500 3/0-500230 400 400 3/0-500 3/0-500380 250 250 #6-350 #6-350460 250 250 #6-350 #6-350575 250 250 #6-350 #6-350Catalog WGS-1 WGS 130A – 190A 35