Ethernet ModulesSpecificationsThe main specifications for the Quantum 1<strong>40</strong>NOE771xx Ethernet Modules aredescribed in the following tableSpecificationsCommunication PortsOne auto-sensing 10/100Base-T shielded twistedpair (RJ-45 connector) port and one 100Base-FX(MT-RJ connector) port. Both ports transmit andreceive Modbus commands encapsulated in TCP/IPprotocol. Only one port can be used at a time.750 mA3.8 WNoneBus Current RequiredPower DissipationFuseProgramming SoftwareType and versionConcept, Ver. 2.2 or higher (NOE77100/10)Concept, Ver 2.5 or higher (NOE77101/11)Modsoft, Ver. 2.6 or higher (NOE77100/10)ProWORX NxT, Ver 2.1 or higher (NOE77100/10)ProWORX NxT, Ver 2.2 or higher (NOE77101/11)FirmwareCPU Type and versionQuantum Executive, Ver. 2.0, or higherNOE UpgradeableField Upgradeable via FTP or Programming Panel.Operating ConditionsTemperature0 to +60° CHumidity0 to 95% Rh non-condensing @ 60° CAltitude 15,000 ft (4500 m)Vibration10-57 Hz @ 0.0075 mm d.a57-150 Hz @ 1 gStorage ConditionsTemperature-<strong>40</strong> to +85°CHumidity 0 to 95% Rh non condensing @ 60°CFree Fall1 m unpackagedShock3 shocks / axis, 15 g, 11 ms8<strong>40</strong> USE 100 00 September 20<strong>02</strong> 319