Instructions for the installer3.27 - TESTING THE IGNITION SAFETYSHUT OFF DEVICE- Power on by switching ON-OFF switch- Check that the boiler is connected to the electricalsupply; the green indicator led “Q” ( ) on the controlpanel must be illuminated.- Create a request in CH by pressing key indicate.- Turn the gas valve knob, in OFF position.- After 1sec, boiler switch off,Lock-out indicatorled illuminated+ fault indicator ledLIGHTBLUE- Press Reset Key will displayed the fault code LF (lossof flame), the boiler will retry ignition cycle (7 seconds)after which if was not removed the cause of the fault(gas tap) the boiler will shut off.38