September-2011<br />

D. Flow <strong>and</strong> pressure requirements shall comply with NFPA 14 except as modified in Section<br />

5.3, <strong>Fire</strong> Pumps.<br />

Note: If the facility is a high-rise building, defined by NFPA 14 as a building more than 75<br />

feet from the lowest level <strong>of</strong> fire department access to the floor <strong>of</strong> the highest occupied level,<br />

an automatic st<strong>and</strong>pipe system is required by NFPA 14. It is the position <strong>of</strong> the VA that the<br />

building fire pump be sized only for the sprinkler system dem<strong>and</strong> <strong>and</strong> to let the fire<br />

department supply the flow <strong>and</strong> pressure for manual fire fighting. The fire pump should be<br />

sized to h<strong>and</strong>le the automatic st<strong>and</strong>pipe fire fighting requirements in NFPA 14 only where<br />

the fire department pumper truck cannot provide the necessary pressure, <strong>and</strong> this is not<br />

anticipated at any VA facility. The designer must verify that the fire department can<br />

adequately supply the manual fire fighting requirements.<br />

E. For seismic requirements, refer to Section 6.1.I.<br />

6.3 Gaseous Systems (Clean Agent, Carbon Dioxide, etc.): Reserved.<br />

6.4 Portable <strong>Fire</strong> Extinguishers:<br />

A. Do not provide fire extinguishers. Locate fire extinguisher cabinets to comply with<br />

NFPA 10. Locate additional fire extinguisher cabinets in the surgical suite, high value IT<br />

(Information Technology) equipment <strong>and</strong> telephone switch rooms, <strong>and</strong> in elevator machine<br />

rooms.<br />

B. Size fire extinguisher cabinets to accommodate a 9.5 L (2-1/2 gallon) pressurized water<br />

extinguisher. Recessed cabinets are preferred. Specify conspicuous marking <strong>of</strong> recessed<br />

cabinets.<br />

6.5 Extinguishing Systems for cooking facilities/equipment: Provide wet chemical fire extinguishing<br />

systems in accordance with UL 300 <strong>and</strong> NFPA 17A. See Section 3.3. Dry chemical systems<br />

shall not be installed.<br />

- 27 ­