Explanation <strong>of</strong> <strong>Fire</strong> Alarm Interface with Elevators<br />
September-2011<br />
Notes:<br />
• There can be many variations <strong>of</strong> the accompanying “Pictorial Representation <strong>of</strong> <strong>Fire</strong> Alarm Interface<br />
with Elevators.”<br />
• In this example, the smoke <strong>and</strong> heat detectors are addressable initiating devices <strong>and</strong> the operating<br />
relays are “hardwired.”<br />
• To achieve supervision, the relay circuits are operated from supervised control circuits. Sometimes<br />
NACs (Notification Appliance Circuits) are used to accomplish this function.<br />
• The supervisory initiating device that monitors the power for the shunt trip circuit is connected to a<br />
supervisory IDC (Initiating Device Circuit).<br />
• The scenario assumes that:<br />
1. There is a sprinklered elevator hoistway.<br />
2. Means to disconnect the main line power to the elevator is via a shunt trip breaker.<br />
3. System operation is in accordance with NFPA 72.<br />
4. Relay (R5) <strong>and</strong> an IDC (Initiating Device Circuit) have been included to provide indication<br />
(via a supervisory alarm) <strong>of</strong> absence <strong>of</strong> voltage (power) to operate shunt trip breaker.<br />
Components Function<br />
R1 --------------- Signal to elevator controller for recall to designated level.<br />
R2 --------------- Signal to elevator controller for recall to alternate level.<br />
R3 --------------- Signal to elevator controller for firefighter notification.<br />
R4 --------------- Signal to activate shunt trip relay.<br />
R5 --------------- Supervisory relay to monitor presence <strong>of</strong> voltage (power) to operate shunt trip<br />
breaker.<br />
SCC1 ----------- Supervised Control Circuit for operating R1.<br />
SCC2 ----------- Supervised Control Circuit for operating R2.<br />
SCC3 ----------- Supervised Control Circuit for operating R3.<br />
SCC4 ----------- Supervised Control Circuit for operating R4.<br />
IDC1------------ Initiating Device Circuit to supervise R5 contacts (monitoring power to operate shunt<br />
trip breaker).<br />
- 42