InstallationAssembly and wiringDimensions and drillingdrilling diagram<strong>Sepam</strong> <strong>2000</strong> is flush-mounted in a rectangularcut-out.Maximum thickness of mounting: 3 mm.mounting lugs (x 2)<strong>Sepam</strong> A (mm) B (mm) C (mm)222201202S26 * 244 250 264S36 * 332 338 352* S25, S35 for earlier versions20 300BCAAssemblyb insert <strong>Sepam</strong> <strong>2000</strong> through the front of the cut-out.Slide it into the cut-out until the front of <strong>Sepam</strong> <strong>2000</strong>is in contact with the mounting plate. The 2 notches(1) at the base of the <strong>Sepam</strong> <strong>2000</strong> case allowit to hold by its own weight.b position the 2 lugs (2) in the holes on the topof <strong>Sepam</strong>. Tighten the threaded studs of the lug.b make sure not to block the ventilation openingson the top and bottom of <strong>Sepam</strong> <strong>2000</strong>. Leave a spaceof at least 5 cm above and below <strong>Sepam</strong>.(2)(2)(1)HV/MV substation Installation - Use - Commissioning1/7