Operation via the pocket terminal onlyfunction TSM 2001 menu name description range accuracyearth fault add. reading Io measurement of residual current 0 to 10 Ino +5%residual currentresidual voltage add. reading Vo measurement of residual voltage 0 to 1.5 Un +5%residual voltagethermal overload thermal protection E thermal capacity used 0 to 999% +2%directional directional O/C Phi 1 phase shift between I1 and I32 0° to 360° +3° at In, Unovercurrent protection Phi 3 phase shift between I3 and U21 0° to 360° +3° at In, Undirectional earth directional E/F protection Phi 0 phase shift between Io and Vo 0° to 360° +3°faultcumulative breaking add. reading cumulative (kA) 2 broken by 5% In to 24 In +10%current and nb. of nb of (kA) 2 breaks breaking current rangebreaksdifferential current add. reading I diff and I through 0 to 24 In +5%and through currenttrue rms current add. reading I rms true rms current up to 0 to 4 In +1%harmonic 21messages program logic AL list of last 16 automation messages 16 messagesevents counter <strong>Sepam</strong> HV Resetline busbar transformerprotection tripping C2 C2 C2 KP49single-phase reclosing C3 KP573-phase reclosing C4 KP57events counter <strong>Sepam</strong> MV Resetsubstation overhead underground capacitor busbardevice switching C1 C1 C1 C1 C1 KP53overcurrent trip C2 C2 C2 C2 C2 KP49fault trip C3 C3 C3 C3 C3 KP49successful reclosing C4 KP54cycle 1 C5 KP54cycle 2 C6 KP54cycle 3 C7 KP54cycle 4 C8 KP54hours counter capacitor <strong>Sepam</strong> Resetcapacitor 1 C4 KP62capacitor 2 C5 KP62capacitor 3 C6 KP62HV/MV substation Installation - Use - Commissioning2/7

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!