<strong>Maintenance</strong>Zone Temperature Sensor (ZTS) TestNote:These procedures are not forprogrammable or digital modelsand are conducted with the ZoneSensorModule electrically removed fromthe system.Test 1Zone Temperature Thermistor(ZTEMP)This component is tested bymeasuring the resistance betweenterminals 1 and 2 on the ZoneTemperature Sensor.Table 55 - Thermistor Resistance /Temperature ChartTemperature/resistance coefficient isnegative.Temperature Resistance(°C)(kOhms)-21 103-15 74.65-9 54.66-7 46.94-4 40.4-1 34.852 30.184 26.227 22.8510 19.9613 17.4716 15.3318 13.4921 11.8924 10.527 9.29729 8.24732 7.3335 6.52838 5.824RT-SVX20B-E465