Product Manual <strong>esco</strong>start DS3 11<br />
3.2.4 Specifications<br />
Supply<br />
Mains voltage (L1, L2, L3)<br />
DS3-400–xxxx .............................................................................................................. 200 VAC ~ 525 VAC (± 10%)<br />
Control voltage (A4, A5, A6)<br />
H .......................................................................................... 110-120 VAC or 220-240 VAC (+ 10% / -15%), 600mA<br />
L .................................................................................................................................................. 24 VAC/VDC ±20%<br />
Mains frequency ......................................................................................................................................... 45 Hz to 66 Hz<br />
Rated insulation voltage to earth ......................................................................................................................... 600 VAC<br />
Rated impulse withst<strong>and</strong> voltage ............................................................................................................................... 4 kV<br />
Form designation .............................................................. Bypassed or continuous, semiconductor motor starter form 1<br />
Short circuit capability<br />
Coordination with semiconductor fuses.................................................................................................................... Type 2<br />
Coordination with HRC fuses ................................................................................................................................... Type 1<br />
DS3-23 to DS3-105 ............................................................................................................ prospective current 10 kA<br />
DS3-145 to DS3-220 .......................................................................................................... prospective current 18 kA<br />
DS3-255N to DS3-930N ..................................................................................................... prospective current 85 kA<br />
DS3-1200N to DS3-1600N ............................................................................................... prospective current 100 kA<br />
Electromagnetic capability (compliant with EU Directive 89/336/EEC)<br />
EMC Emissions................................................................... IEC 60947-4-2 Class B <strong>and</strong> Lloyds Marine No 1 Specification<br />
EMC Immunity.............................................................................................................................................. IEC 60947-4-2<br />
Inputs<br />
Input rating ........................................................................................................................... Active 24 VDC, 8 mA approx<br />
Start (54, 55) .............................................................................................................................................. Normally open<br />
Stop (56, 57) ............................................................................................................................................ Normally closed<br />
Reset (58, 57) .......................................................................................................................................... Normally closed<br />
Programmable input (53, 55) ..................................................................................................................... Normally open<br />
Motor thermistor (64, 65) ........................................................................................................ Trip >3.6 k�, reset