Product Manual <strong>esco</strong>start DS3 21<br />

5.1.6 Inside delta installation, non-bypassed<br />

KM1 F1<br />

KM1 Main contactor<br />

F1 Semiconductor fuses (optional)<br />

04483.C<br />

1/L1<br />

3/L2<br />

5/L3<br />

Product Manual <strong>esco</strong>start DS3 21<br />

2/T1<br />

4/T2<br />

6/T3<br />

13<br />

14<br />

KM1<br />

U1(1) U2(4)<br />

M<br />

V1(2) V2(5)<br />

3ph.<br />

3<br />

W1(3) W2(6)<br />

CAUTION<br />

When connecting the <strong>esco</strong>start DS3 in inside delta configuration, <strong>always</strong> install a main contactor or<br />

shunt trip circuit breaker.<br />

5.2 Bypass Contactor<br />

<strong>esco</strong>start DS3 soft starters with model num<strong>be</strong>rs <strong>esco</strong>start DS3 23 ~ <strong>esco</strong>start DS3 220 are internally<br />

bypassed <strong>and</strong> do not require an external bypass contactor.<br />

<strong>esco</strong>start DS3 soft starters with model num<strong>be</strong>rs <strong>esco</strong>start DS3 255N ~ <strong>esco</strong>start DS3 1600N are not internally<br />

bypassed <strong>and</strong> may <strong>be</strong> installed with an external bypass contactor. Select a contactor with an AC1 rating<br />

greater than or equal to the full load current rating of the connected motor.<br />

5.3 Main Contactor<br />

A main contactor <strong>must</strong> <strong>be</strong> installed if the <strong>esco</strong>start DS3 is connected to the motor in inside delta format <strong>and</strong> is<br />

optional for in-line connection. Select a contactor with an AC3 rating greater than or equal to the full load<br />

current rating of the connected motor.<br />

5.4 Circuit Breaker<br />

A shunt trip circuit breaker may <strong>be</strong> used instead of a main contactor to isolate the motor circuit in the event of<br />

a soft starter trip. The shunt trip mechanism <strong>must</strong> <strong>be</strong> powered from the supply side of the circuit breaker or<br />

from a separate control supply.<br />

5.5 Power Factor Correction<br />

If power factor correction is used, a dedicated contactor should <strong>be</strong> used to switch in the capacitors.<br />

CAUTION<br />

Power factor correction capacitors <strong>must</strong> <strong>be</strong> connected to the input side of the soft starter.<br />

Connecting power factor correction capacitors to the output side will damage the soft starter.