Product Manual <strong>esco</strong>start DS3 49<br />
4G – Frequency Check<br />
4H – Frequency Variation<br />
8.1.5 Protection Delays<br />
5A – Restart Delay<br />
5B – Current Imbalance Delay<br />
5C – Undercurrent Delay<br />
Range: Do Not Check<br />
Start Only<br />
Start/Run (Default)<br />
Run Only<br />
Description: Determines when <strong>and</strong> if the starter will<br />
monitor for a frequency trip.<br />
Range: ± 2 Hz<br />
± 5 Hz (Default)<br />
± 10 Hz<br />
± 15 Hz<br />
5D – Instantaneous Overcurrent Delay<br />
5E – Input A Trip Delay<br />
Description: Selects the soft starter's tolerance for<br />
frequency variation.<br />
Range: 00:01 - 60:00 (minutes:seconds) Default: 10<br />
seconds<br />
Description: The <strong>esco</strong>start DS3 can <strong>be</strong> configured to<br />
force a delay <strong>be</strong>tween the end of a stop <strong>and</strong> the <strong>be</strong>ginning of the next start.<br />
During the restart delay period, the display shows the time remaining <strong>be</strong>fore<br />
another start can <strong>be</strong> attempted.<br />
Range: 0:00 - 4:00 (minutes:seconds) Default: 3 seconds<br />
Description: Slows the <strong>esco</strong>start DS3 response to<br />
current imbalance, avoiding trips due to momentary fluctuations.<br />
Range: 0:00 - 4:00 (minutes:seconds) Default: 5 seconds<br />
Description: Slows the <strong>esco</strong>start DS3 response to<br />
undercurrent, avoiding trips due to momentary fluctuations.<br />
Range: 0:00 - 1:00 (minutes:seconds) Default: 0 seconds<br />
Description: Slows the <strong>esco</strong>start DS3 response to<br />
overcurrent, avoiding trips due to momentary overcurrent events.<br />
Range: 0:00 - 4:00 (minutes:seconds) Default: 0 seconds<br />
Description: Sets a delay <strong>be</strong>tween the input activating<br />
<strong>and</strong> the soft starter tripping.<br />
Product Manual <strong>esco</strong>start DS3 49