Product Manual <strong>esco</strong>start DS3 49<br />

4G – Frequency Check<br />

4H – Frequency Variation<br />

8.1.5 Protection Delays<br />

5A – Restart Delay<br />

5B – Current Imbalance Delay<br />

5C – Undercurrent Delay<br />

Range: Do Not Check<br />

Start Only<br />

Start/Run (Default)<br />

Run Only<br />

Description: Determines when <strong>and</strong> if the starter will<br />

monitor for a frequency trip.<br />

Range: ± 2 Hz<br />

± 5 Hz (Default)<br />

± 10 Hz<br />

± 15 Hz<br />

5D – Instantaneous Overcurrent Delay<br />

5E – Input A Trip Delay<br />

Description: Selects the soft starter's tolerance for<br />

frequency variation.<br />

Range: 00:01 - 60:00 (minutes:seconds) Default: 10<br />

seconds<br />

Description: The <strong>esco</strong>start DS3 can <strong>be</strong> configured to<br />

force a delay <strong>be</strong>tween the end of a stop <strong>and</strong> the <strong>be</strong>ginning of the next start.<br />

During the restart delay period, the display shows the time remaining <strong>be</strong>fore<br />

another start can <strong>be</strong> attempted.<br />

Range: 0:00 - 4:00 (minutes:seconds) Default: 3 seconds<br />

Description: Slows the <strong>esco</strong>start DS3 response to<br />

current imbalance, avoiding trips due to momentary fluctuations.<br />

Range: 0:00 - 4:00 (minutes:seconds) Default: 5 seconds<br />

Description: Slows the <strong>esco</strong>start DS3 response to<br />

undercurrent, avoiding trips due to momentary fluctuations.<br />

Range: 0:00 - 1:00 (minutes:seconds) Default: 0 seconds<br />

Description: Slows the <strong>esco</strong>start DS3 response to<br />

overcurrent, avoiding trips due to momentary overcurrent events.<br />

Range: 0:00 - 4:00 (minutes:seconds) Default: 0 seconds<br />

Description: Sets a delay <strong>be</strong>tween the input activating<br />

<strong>and</strong> the soft starter tripping.<br />