Product Manual <strong>esco</strong>start DS3 45<br />

2G – Excess Start Time<br />

Excess start time is the maximum time the <strong>esco</strong>start DS3 will attempt to start the motor. If the motor<br />

does not transition to Run mode within the programmed limit, the starter will trip. Set for a period<br />

slightly longer than required for a normal healthy start. A setting of 0 disables excess start time<br />

protection.<br />

2H – Stop Mode<br />

2I – Stop Time<br />

2J Adaptv Start Profile<br />

2K – Adaptv Stop Profile<br />

2L – Adaptv Control Gain<br />

Range: 0:00 - 4:00 (minutes:seconds) Default: 20 seconds<br />

Description: Set as required.<br />

Options: Coast To Stop (Default)<br />

TVR Soft Stop<br />

Adaptive Control<br />

Brake<br />

Description: Selects the stop mode.<br />

Range: 0:00 - 4:00 (minutes:seconds) Default: 0 seconds<br />

Description: Sets the time for soft stopping the motor<br />

using timed voltage ramp or Adaptive Control (AAC).<br />

If a main contactor is installed, the contactor <strong>must</strong> remain closed until the end of<br />

the stop time. Use a programmable output configured to Run to control the main<br />

contactor. Sets the total stopping time when using brake.<br />

Options: Early Acceleration<br />

Constant Acceleration (Default)<br />

Late Acceleration<br />

Description: Selects which profile the <strong>esco</strong>start DS3<br />

will use for an AAC Adaptive Acceleration Control soft start.<br />

Options: Early Deceleration<br />

Constant Deceleration (Default)<br />

Late Deceleration<br />

Description: Selects which profile the <strong>esco</strong>start DS3<br />

will use for an AAC Adaptive Deceleration Control soft stop.<br />

Range: 1% - 200% Default: 75%<br />

Description: Adjusts the performance of AAC<br />

Adaptive Control. <strong>This</strong> setting affects both starting <strong>and</strong> stopping control.<br />

NOTE: We recommend leaving the gain setting at the default level unless performance is not<br />

satisfactory. If the motor accelerates or decelerates too quickly at the end of a start or stop,<br />

increase the gain setting by 5%~10%. If the motor speed fluctuates during starting or stopping,<br />

decrease the gain setting slightly.<br />

Product Manual <strong>esco</strong>start DS3 45