Product Manual <strong>esco</strong>start DS3 43<br />
8. Parameter Descriptions<br />
8.1.1 Motor Details<br />
1A – Motor FLC<br />
1B – Locked Rotor Time<br />
1C – Motor FLC-2<br />
1D – Locked Rotor Time-2<br />
1E – Dual Thermal Model<br />
Range: Model dependent<br />
Description: Matches the starter to the connected<br />
motor's full load current. Set to the full load current (FLC) rating shown on the<br />
motor nameplate.<br />
Range: 0:01 - 2:00 (minutes:seconds) Default: 10 seconds<br />
Description: Sets the maximum length of time the<br />
motor can run at locked rotor current from cold <strong>be</strong>fore reaching its maximum<br />
temperature. Set according to the motor datasheet.<br />
Range: Model dependent<br />
Description: Sets the secondary motor's full load<br />
current.<br />
Range: 0:01 - 2:00 (minutes:seconds) Default: 10 seconds<br />
Description: Sets the maximum length of time the<br />
motor can run at locked rotor current from cold <strong>be</strong>fore reaching its maximum<br />
temperature. Set according to the motor datasheet.<br />
Options: Single (Default)<br />
Dual<br />
Description: Activates dual thermal modeling. The<br />
dual thermal model is required only if the <strong>esco</strong>start DS3 is controlling two<br />
physically separate motors.<br />
NOTE<br />
The second thermal model is only active if parameter 1E Dual Thermal Model is set to 'Dual' <strong>and</strong> the<br />
starter is using the secondary motor set (a programmable input is set to 'Motor Set Select' <strong>and</strong> the<br />
input is active).<br />
Product Manual <strong>esco</strong>start DS3 43