4 th Digit – Cycles available to the operator0 No cycles availableRemote setpoint enabled1…9 1..8 cycles available for the operatorSelect 9 for 15 cycles / 20 steps eachP-02 Configuration analog input AN1Select type of thermocouple or RTD connected to input AN1,visualization range and process corresponding to this input.1 st Digit – Type of sensor0 Not used1 Thermocouple or RTD (selected on 2 nd digit)2 nd Digit – Type of thermocouple/RTD0 Type K (-250/1350°C)1 Type S (-50/1750°C)2 Type T (-250/400°C)3 Type R (-50/1750°C)4 Type J (-200/1000°C)5 Type E (-250/1000°C)6 PT100 (-100/600°C)7 NI100 (-60/180°C)3 rd Digit – Decimal point0 No decimal point1 Visualization with decimal point4 th Digit – Select corresponding process0 Process 11 Process 2P-03 Configuration of analog input AN2Select type of thermocouple or signal V/mA connected to inputAN2, visualization range and process corresponding to this input1 st Digit – Type of sensor0 Not used1 Thermocouple (selected on 2 nd digit)2 Tension 0-1V3 Tension 0-10V4 Current 0-20mA5 Current 4-20mA2 nd Digit – Type thermocouple/RTD0 Type K (-250/1350°C)1 Type S (-50/1750°C)76