Functions<br />

Transmission medium<br />

Mechanical design<br />

<strong>Konnex</strong> TP1<br />

Bus cable selection<br />

Screened <strong>bus</strong> cable<br />

2/10<br />

The <strong>Konnex</strong> <strong>bus</strong> serves as a transmission medium:<br />

• To commission and remote control the Synco 700 controllers and the Synco RXB<br />

room controllers by means of the service tool OCI700.1<br />

• To exchange process data between the Synco devices<br />

The simplest form of the "<strong>Konnex</strong> TP1" <strong>bus</strong> comprises a two-core <strong>bus</strong> cable with<br />

stranded lines CE+ (red) and CE– (black).<br />

CE+<br />

CE−<br />

CE+ Red line<br />

CE+ Black line<br />

W Protective layer<br />

W<br />

Select the <strong>bus</strong> cable according to the country-specific offerings by adhering to the<br />

values indicated in the "Technical data" section. Bus cables available in EIB market<br />

countries as per the specifications are:<br />

• YCYM 2x2x0.8 Fixed installation<br />

EIB specification Dry, humid, wet rooms<br />

Outdoors (not exposed to sunlight)<br />

Surface mounted, flush mounted, in pipes<br />

• J-Y(St)Y 2x2x0.8 Fixed installation<br />

EIB specification Indoors only<br />

Surface mounted, in pipes<br />

• JH(St)H2x2x0.8 Halogen-free conductor, laid separately<br />

• A-2Y(L)2Y or A-2YF(L)2Y Underground cable for remote transmission, outdoors<br />

Synco or the <strong>Konnex</strong> <strong>bus</strong> allows for <strong>bus</strong> cables without screening. The screens<br />

available for EIB <strong>bus</strong> cables normally do not need to be connected.<br />

If you use a screened <strong>bus</strong> cable due to expected noise, connect the screen by following<br />

standard installation rules.<br />

<strong>Siemens</strong> Building Technologies Data sheet <strong>Konnex</strong> <strong>bus</strong> Preliminary Editon 17.01.2003 CE1N<strong>3127</strong>en<br />

HVAC Products 17.01.2003<br />

<strong>3127</strong>Z05de